16 POINTBlock dc 8 Input/8 Relay Output Module
Publication
1734-IN021C-EN-P - September 2006
Field Power Bus
Supply Voltage, Nom
Voltage Range
Supply Current, Max
24V dc
10…28.8V dc
10 A
Communication Rate
125 Kbps (500 m max)
250 Kbps (250 m max)
500 Kbps (100 m max)
Dimensions (HxWxD),
Approx.
76.2 x 60.0 x 33.4 mm (3.00 x 2.36 x 5.25 in.)
Conductors Wire Size
Category
0.25…2.5 mm
2
(22…14 AWG), solid or stranded copper
rated @ 75 °C (167 °F) or higher
1.2 mm (3/64 in.) insulation max
2 - on all ports
(2)
Terminal Base Screw
Torque
0.5…0.6 Nm (5…7 lb-in)
North American Temp
Code
T5
Field Wiring Terminations
DeviceNet
1 - Black Wire-V
2 - Blue WireCAN Low
3 - Bare WireDrain
4 - White WireCAN High
5 - Red Wire+V
Field Power Supply
0 - No Connection 1 - No Connection
2 - No Connection 3 - No Connection
4 - Common 5 - Common
6 - Supply 7 - Supply
Weight, Approx.
0.40 kg (0.86 lb)
(1)
350 mA for max with expansion of 12 POINT I/O modules
(2)
Use this conductor category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-IN041.
POINTBlock dc 8 Input/8 Relay Output Module - 1734D-IB8XOW8,
1734D-IB8XOW8S
Attribute
Value