Devicenet connector wiring, Specifications – Rockwell Automation 1734D-1B8XOW8S 8 Input/8 Relay Output Module Installation Instructions User Manual
Page 15
POINTBlock dc 8 Input/8 Relay Output Module 15
Publication
1734-IN021C-EN-P - September 2006
DeviceNet Connector Wiring
Specifications
IMPORTANT
When connecting more than one wire in a termination point,
make sure that both wires are the same gauge and type.
POINTBlock dc 8 Input/8 Relay Output Module - 1734D-IB8XOW8,
1734D-IB8XOW8S
Attribute
Value
POINTBus Output Current
1 A max @ 5V dc output
DeviceNet Current
(1)
95 mA max for POINTBlock
Number of POINT I/O
Expansion Modules
12 max at expansion port
Isolation Voltage
120V (continuous), Reinforced Insulation Type
1250V rms or 2121V dc for 1 s between ac circuits and
DeviceNet network
Indicators
1 red/green module status indicator
1 red/green network status indicator
16 I/O status indicators (8 input/8 relay output)
Power Dissipation
2.0 W max @ 24V dc
Power Consumption
8.2 W max @ 24V dc
DeviceNet
Connection
Red
White
Bare
Blue
Black
-V
42132
+V
CAN - High
Shield
CAN - Low