B - application guidelines and tips, Cached and uncached connections, Appendix b – Rockwell Automation 1756-DHRIO_DHRIOXT ControlLogix Data Highway Plus-Remote I/O Communication Interface Module User Manual
Page 163: Application guidelines and tips, Appendix
![background image](/manuals/579701/163/background.png)
Rockwell Automation Publication 1756-UM514C-EN-P - June 2014
163
Appendix
B
Application Guidelines and Tips
Use this appendix to better understand how to use your 1756-DHRIO and
1756-DHRIOXT modules in DH+ and remote I/O applications.
Cached and Uncached
Connections
A connection is defined as a message from point A to point B. A ControlLogix
controller can make a total of 250 connections. With RSLogix 5000 version 10
or later, the controller can cache a total of16 DH+ connections and 16 remote
I/O connections. In RSLogix 5000 versions 9 and earlier, the controller can cache
only remote I/O connections.
Up to five messages can be sent between points and be counted as one
connection. When you read and write to the same module on remote I/O,
however, you must interlock messages.
The two types of connections in DH+ and remote I/O applications are as
follows:
•
•
Topic
Page
Cached and Uncached Connections
ControlLogix Controller Constraints
Messages Between a ControlLogix Controller and PLC
Devices
RPI Formula without Block Transfer Modules
Increase the Unconnected Message Buffer Limit
Remote I/O Performance: ControlLogix Controllers versus
PLC-5 Controllers