Troubleshooting the Module
Chapter 13
Alphanumeric Indicator Status Message - Remote I/O
If the OK indicator is:
Module status is:
Take this action:
MUTE
LINK
No adapters found on remote I/O.
Add an adapter to the remote I/O
network.
RACK
OVER
Rack overlap on remote I/O.
Reconfigure remote I/O racks.
DUPL
SCAN
Duplicate scanner on remote I/O.
Check remote I/O adapter settings.
MAX_
DEV_
Maximum devices exceeded on remote
I/O.
Remove devices to meet limitations on
remote I/O network.
CHAT
LINK
Babble detected on remote I/O.
Check remote I/O device and network
connections.
OFF_
LINE
Not trying to communicate.
None. Normal state if controller is not
controlling remote I/O.
OK
Normal operation for that channel.
None.
Module Status - OK Indicator
If the OK indicator is:
Module status is:
Take this action:
Off
Not operating.
Apply chassis power. Verify module is
completely inserted into chassis and
backplane.
Green flashing
Operating, but not routing messages
and no controller transferring I/O.
None, if no messages are actively being
routed through the module and no
controller transferring I/O.
To route messages or transfer I/O, use
module default configuration or
configure module.
Red, then Off
Performing self-test.
None, normal operation.
Green
Operating and routing messages.
Verify module configuration.
Red
In major fault.
Restart module. If red reoccurs, replace
module.
Red flashing
In major fault or configuration fault.
Check alphanumeric indicator and take
action described in Alphanumeric
Indicator Status Message table.