beautypg.com

Specifications – Rockwell Automation 1756-ENBT ControlLogix EtherNet/IP Bridge Module Installation Instructions User Manual

Page 18

background image

18 ControlLogix EtherNet/IP Bridge Module

Publication

1756-IN019C-EN-P - November 2004

Specifications

Module Location

Any slot in the ControlLogix chassis

Backplane Current (mA)
at 5V.1V dc

700mA

Backplane Current (mA)
at 24V

3mA

Isolation Voltage,
Continuous

30V

Tested to 707V dc for 60 seconds

Power Dissipation, Max.

3.65W

Conductors

Wire Size
Category

802.3 compliant - shielded or unshielded twisted pair

2

1

Ethernet Connector

RJ45 Cat. 5

User Manual

ENET-UM001

Environmental Conditions

Operating
Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 60°C (32 to 140°F)

Storage
Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
–40 to 85°C (–40 to 185°F)

Relative
Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp
Heat):
5 to 95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
2g @ 10-500Hz

Shock,
Operating

IEC60068-2-27 (Test Ea, Unpackaged shock):
30g