Link Status Indicator

The Link Status LED provides the following information:

OK Status Indicator

The OK Status LED provides the following module information:

Where to Find Information on Configuring the Module

To configure your module, refer to the configuration chapter of your
EtherNet/IP Modules User Manual, publication number ENET-UM001,
available online at www.rockwellautomation.com/literature.

State

Status

Description

Off

No data transmission

Module is not ready to communicate.

Green

Ready

Module is ready to communicate.

Flashing Green

Data transmission in
progress

Module is communicating over the
network.

State

Status

Description

Off

No Power

Module does not have 24V DC power.
Verify there is chassis power and the
module is completely inserted into
chassis and backplane.

Flashing Green

Standby

Module is not configured.

Green

Operational

Module is operating correctly.

Flashing Red

Minor Fault

A recoverable fault has been detected.
This could be caused by an error in the
configuration.

Red

Major Fault

An unrecoverable fault has been
detected. Recycle power to the module.
If this does not clear the fault, replace
the module.

Flashing Red and Green Self Test

Module performing power-up self-test.