16 ControlLogix EtherNet/IP Bridge Module

Publication

1756-IN019C-EN-P - November 2004

Troubleshoot the Module

If the alphanumeric display and LED indicators do not sequence through the
expected states refer to the following troubleshooting tables. The three
bi-color (red/green) LED status indicators on the 1756-ENBT module
provide diagnostic information about the module and its connections to the
network.

NET (Network) Status Indicator

The Network Status LED provides the following information:

State

Status

Description

Off

Not Powered,

No IP Address

Module is not powered, or does not
have an IP address.
• Verify there is chassis power and

the module is completely inserted
into the chassis and backplane.

• Make sure the module has been

configured.

Flashing Green

No Connections

Module has obtained an IP address,
but has no established connections.

Green

CIP Connections

Module has an IP address and at least
one established connection.

Flashing Red

Connection Timeout

One or more of the connections in
which the module is the target has
timed out.

Red

Duplicate IP Address

Module has detected that its IP
address is already in use. Assign a
unique IP address to the module.