Rockwell Automation Logix5000 Controllers Major, Minor, and I/O Faults Programming Manual User Manual
Page 46
Chapter 3 I/O fault codes
Code
Interpretation
#0306
The ControlNet Configuration Master (CCM) cannot be found. The 1756-CNB module and PLC-5 ControlNet processor are the only devices capable of being a CCM and
the CCM must be node 1.
Verify that a 1756-CNB modules or PLC-5 ControlNet processor is at node 1 and is functioning properly.
This fault may temporarily occur when the system is powered up and is being cleared when the CCM is located.
#0311
The controller is attempting to set up a connection with the module and has received an error.
Verify that all modules in the I/O Configuration tree are the correct modules.
#0312
The controller is attempting to set up a connection with the module and has received an error: an invalid link address has been specified. A link address can be a slot
number, a network address, or the remote I/O chassis number and starting group.
Verify that the chosen slot number for this module is not greater than the size of the rack.
Verify that the ControlNet node number is not greater than the maximum node number configured for the network in RSNetWorx for ControlNet software.
#0315
The segment type or route is invalid.
Possible causes include the following.
•
The controller is attempting to set up a connection with the module and has received an error: the connection request is invalid.
•
The module in use (that is, the physical module) is different than the module specified in the I/O configuration tree and is therefore causing the connection or service
to fail.
The fault may occur even when the module passes the electronic keying test. This may result when Disable Keying or Compatible Keying options are used in the
module configuration instead of the Exact Match option.
Despite passing the electronic keying test, the module being connected does not have the same features or settings as the module specified in the I/O configuration
tree and does not support the connection or service being attempted.
Check the module in use and verify that it exactly matches the module specified in the I/O configuration tree of the Logix Designer application.
For more information about electronic keying, see the user manual for the module you are using.
#0317
The controller is attempting to set up a ControlNet connection with the module and has received an error.
Use RSNetWorx for ControlNet software to schedule or reschedule the connection to this module.
#0318
The controller is attempting to set up a connection with the module and has received an error: the link address is invalid.
Verify that the associated ControlNet module has the correct slot or node number selected.
#0319
The controller is attempting to set up a connection with the module and has received an error: the redundant module does not have the necessary resources to support
the connection.
Reduce the size or number of connections through this module or add another controller or ControlNet module to the system.
#0322
A connection point mismatch has occurred.
Possible causes include the following.
•
A new connection requested does not match the existing connection. Check the controllers that are using the connection and verify that all the configurations are
identical.
•
The connection requested is not a listener or a controlling connection type.
#031E
The controller is attempting to connect to a tag in a producing controller and has received an error.
The controller is attempting to connect to a tag in a producing controller and that tag has already been used by too many consumers. Increase the maximum number of
consumers on the tag.
#031F
No SC (servicing controller) connection object was found that corresponds to a symbol instance.
#0800
No interpretation available.
#0801
No interpretation available.
#0814
Invalid connection status information was found.
#FD01
I/O map object attributes were found to be invalid. A fault has occurred while clearing memory.
#FD02
No error code is supplied by an I/O module to describe an I/O fault.
#FD03
The controller is attempting to set up a connection with the module and has received an error: this module requires a particular set of connections and connection types,
and one of those connection types is missing.
#FD04
The module requires a Coordinated System Time (CST) master in the chassis.
Configure a module (typically a controller) in this chassis to be the CST master.
46
Rockwell Automation Publication 1756-PM014G-EN-P – October 2014