Specifications – Rockwell Automation 1771-SDN DeviceNet Scanner Module Installation Instructions User Manual
Page 39
Publication 1771-IN014B-EN-P - September 2001
DeviceNet Scanner Module Catalog Number 1771-SDN/C 39
Specifications
Module Location
1771-A1B through -A4B or later I/O chassis
Module Defaults
Node Address – 63
Baud Rate – 125 Kbits/s
Power Consumption
- Backplane Current
- DeviceNet
1
5Vdc, 0.8A
24Vdc, 50mA per channel Class 2
Isolation Voltage
Optical Isolation between backplane and DeviceNet channel,
tested to withstand 500Vac for 60 seconds
1 Megohm resistor from DeviceNet channel to chassis
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0-60
o
C (32–140
o
F)
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bc, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
–40 to 85
o
C (–40 to 185
o
F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating
Damp Heat):
5–95% non condensing
Vibration
IEC60068-2-6 (Test Fc, Operating):
2g @10–500Hz
Shock
IEC60068-2-27:1987, Test Ea (Unpackaged shock, ES#002)
Operating - 30g
Non-operating - 50g
Emissions
CISPR 11:
Group 1, Class A
ESD Immunity
IEC 61000-4-2:
4kV contact discharges
Radiated RF Immunity
IEC 61000-4-3:
10V/m, 3V/m Broadcast Bands, with 1kHz sine-wave 80% AM
from 30MHz to 1000Mhz
EFT/B Immunity
IEC 61000-4-4:
+2kV at 5kHz on communications ports
Surge Transient Immunity
IEC 61000-4-5:
+2kV line-earth(CM)
on signal ports
Conducted RF Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz
to 30MHz
Enclosure Type Rating
None (open style)
Wiring
- Type
- Category
2
1771-CD
2
10-pin Linear Plug
- Torque
- Catalog Number
5-7 pound-inches
1787-PLUG10R
Dimesions (HxWxD)
270 x 30 x 170mm (10.6 x 1.2 x 6.7 inches)
Weight
0.9kg (1.9lb)
1
To remain compliant with UL/CSA certification, the DeviceNet power supply must meet NEC Class 2
requirements.
2
Use this conductor category information for planning conductor routing as described in publication
1770-4.1,
Industrial Automation Wiring and Grounding Guidelines.
Specifications continued on back page