Programming a simple ladder rung – Rockwell Automation 1747-PTxx Getting Started Guide for HHT User Manual
Page 36

Chapter 3
Creating a Program
Getting Started Guide
for HHT
3–11
Programming a Simple Ladder Rung
The following rung consists of an XIC input instruction and an OTE output
instruction. The addresses conform to the controller configuration indicated
in the “Arbitrary Controller” section of this chapter. If you have entered a
different controller configuration, make certain that the addresses are
consistent with your configuration. It is also important that you have an
external input, such as a pushbutton, and an external output, such as a pilot
light, at the terminal addresses used. You will be using these external
devices in later chapters of this guide.
] [
I:1.0
0
( )
O:3.0
0
Entering a Rung
To enter the rung, do the following:
1. Begin where we ended on the previous page, at the program directory
display.
2. Press
[F3] – EDT_FIL
. The following display appears.
File Name:
Prog Name:1000
File Name
Type Size(Instr)
0
System *
1
Reserved *
2
Ladder *
ENTER FILE NUMBER:
F1
F2
F3
F4
F5
OFL
We want to edit file number 2, our main program file.
3. Press
[2] [ENTER]
. The display shows the END rung of a program. No
other rungs exist at this time. The numbers
2.0.0.0.*
appear in the
upper right corner of the display. This indicates that we are in File 2, and
the cursor is located on rung 0, branch 0.
F1
F2
F3
F4
F5
2.0.0.0.*
INS_RNG MOD_RNG SEARCH
DEL_RNG UND_RNG
OFL
>
<END>
4. Press
[F1] – INS_RNG
. The following display appears:
F1
F2
F3
F4
F5
2.0.0.0.*
INS_INST
BRANCH
MOD_INST
ACP_RNG
OFL
>
<END>