Module calibration, Chapter – Rockwell Automation 1771-IXE/D Thermocouple/Millivolt Input Module User Manual User Manual
Page 41
![background image](/manuals/579381/41/background.png)
Chapter
6
Publication 1771Ć6.5.130 Ć May 1999
Module Calibration
In this chapter we tell you how to calibrate your module.
In order to calibrate your input module you will need the following
tools and equipment:
Tool or Equipment
Description
Model/Type
Available from:
Precision Voltage Source
0-100mV, 1
µ
V resolution
Analogic 3100, Data Precision
8200 or equivalent
Industrial Terminal and
Interconnect Cable
Programming terminal for A-B
family processors
Cat. No. 1770-T3 or Cat. No.
1784-T45, -T47, -T50, etc.
Allen-Bradley Company
Highland Heights, OH
The thermocouple/millivolt input module is shipped already
calibrated. If it becomes necessary to recalibrate the module, you
must calibrate the module in an I/O chassis. The module must
communicate with the processor and industrial terminal.
Before calibrating the module, you must enter ladder logic into the
processor memory, so that you can initiate BTWs to the module, and
the processor can read inputs from the module.
Calibration can be accomplished using either of two methods:
•
auto–calibration
•
manual calibration
Auto–calibration calibrates the input by generating offset and gain
correction values and storing them in EEPROM. These values are
read out of EEPROM and placed in RAM memory at initialization of
the module.
The auto–calibration routine operates as follows:
•
Whenever a block transfer write (BTW) of length 28 is
performed to the module (any time after the module has been
powered up), it interrogates word 28 for a request for
auto–calibration.
•
The request can be for the following: offset calibration, gain
calibration, save operation (save to EEPROM).
When using auto–calibration, write transfer calibration words
20 through 27 must contain zeroes.
Chapter Objective
Tools and Equipment
Calibrating Your Input
Module
About AutoĆCalibration