Specifications – Rockwell Automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output User Manual
Page 19
![background image](/manuals/579325/19/background.png)
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input and Output Modules 19
Publication 1732E-IN006C-EN-E - June 2013
Specifications
I/O status
Off
The input or output channel is inactive, can be calibrated.
Flashing Green
Channel is calibrating.
Green
1732E-IF4M12R – Normal operation, inputs being scanned.
1732E-OF4M12R – The output is active and under control.
Flashing Red
1732E-IF4M12R – Fault. Channel is at end of range.
1732E-OF4M12R – Output fault. The output is open (current
mode only), or a low/high clamp alarm is present.
Red
1732E-OF4M12R – Auxiliary power disconnected or off.
IMPORTANT
The Module Status LED indicator will flash red and green for a maximum
30 s while the module completes its POST (Power-On Self Test).
General Specifications
Attributes
Value
Voltage, power, max
30V DC
Voltage, power, min
12V DC
Module power
12…30V DC @ 300 mA
Power consumption
3 W @ 24V DC, typical
3.5 W, max (module unloaded)
Isolation voltage
50V (continuous), Basic Insulation Type
Type tested @ 707V DC for 60 s
Communication rate
EtherNet/IP
10/100 Mbps
Full or half-duplex
100 meter per segment
Status indicators
Module status – red/green
Network status – red/green
Link status – green/yellow
Auxiliary power status – green
I/O LED – red/green
Indicator Status for Modules
Indicator
Status
Description