background image

20 POINT I/O™ 5V and 24V Encoder/Counter Modules

Publication 1734-IN005G-EN-E - September 2012

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…55 °C (-4…131 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):

5…95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

EC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, nonoperating

EC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR11

Group 1, Class A

ESD immunity

IEC6100-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM @ 30…2000 MHz

10V/m with 200 Hz 50% pulse 100% AM @ 900 MHz

EFT/B immunity

IEC 61000-4-4:

±4 kV at 2.5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5:

±1 kV line-line (DM) and

±2 kV line-earth (CM) on signal ports

Conducted RF immunity

IEC61000-4-6: