General specifications – Rockwell Automation 1734-IK/C POINT I/O 5V and 24V Encoder/Counter Module Installation Instructions User Manual
Page 19
![background image](/manuals/579241/19/background.png)
POINT I/O™ 5V and 24V Encoder/Counter Modules 19
Publication 1734-IN005G-EN-E - September 2012
On-state voltage, max
See the
diagram.
Input filter selections
Off
10
μ
s
100
μ
s
1.0 ms
10.0 ms
Input frequency, max
1.0 MHz counter and encoder X1 configurations
500 kHz encoder X2 configuration (no filter)
250 kHz encoder X4 configuration (no filter)
General Specifications
Attribute
Value
Terminal base screw torque
0.6 Nm (7 lb-in.)
Module location
1734-TB, 1734-TBS, 1734-TB3, 1734-TB3S wiring base assembly
POINTBus current, max
160 mA
Power dissipation, max
1734-IJ – 1.1 W @ rated load
1734-IK – 1.5 W @ rated load
Thermal dissipation, max
1734-IJ – 3.75 BTU/hr @ rated load
1734-IK – 5.1 BTU/hr @ rated load
Isolation voltage (continuous-voltage
withstand rating)
50V
Type tested @ 1100V DC for 60 s, field-side to system
External DC power
No additional external power required to power module
Dimensions, approx., HxWxD
56.0 x 12.0 x 75.5 mm
(2.21 x 0.47 x 2.97 in.)
Wiring category
(1)
1 – on signal ports
Wire size
0.25…2.5 mm
2
(22…14 AWG) solid or stranded copper wire rated
at 75 °C (167 °F), or greater, 1.2 mm (3/64 in.) insulation max
Weight, approx.
0.36 kg (0.08 lb)
Keyswitch position
2
Enclosure type rating
None (open-style)
IEC temperature code
T4
North American temp code
T4A
(1)
Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring
and Grounding Guidelines, publicatio
POINT I/O 5V and 24V Encoder/Counter Module – 1734-IK
Attribute
Value