Controller specifications – Rockwell Automation 1785-Lx0E Ethernet PLC-5 Programmable Controllers Installation Instructions User Manual
Page 24

Publication 1785-IN063B-EN-P - January 2006
24 Ethernet PLC-5 Programmable Controllers
Controller Specifications
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0...60
o
C (32...140
o
F)
Nonoperating Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Nonoperating Cold),
IEC 60068-2-2 (Test Bc, Un-packaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Nonoperating Thermal Shock):
–40...85
o
C (–40...185
o
F)
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Nonoperating
Damp Heat):
5...95% Noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10...500Hz
Operating Shock
IEC 60068-2-27:1987, (Test Ea, Unpackaged shock):
30 g
Nonoperating Shock
IEC 60068-2-27:1987, (Test Ea, Unpackaged shock):
50 g
Emissions
CISPR 11:
Group 1, Class A (with appropriate enclosure)
ESD Immunity
IEC 61000-4-2:
6 kV indirect contact discharges
Radiated RF Immunity
IEC 61000-4-3:
10 V/m with 1 kHz sine-wave 80% AM from 30...2000 MHz
10 V/m with 200 Hz Pulse 50% AM from 100% AM at 900 MHz
10 V/m with 200 Hz Pulse 50% AM from 100% AM at 1890 MHz
1V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz
EFT/B Immunity
IEC 61000-4-4:
+2 kV at 5 kHz on communications ports
Surge Transient Immunity
IEC 61000-4-5:
+2 kV line-earth (CM) on communications ports
Conducted RF Immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Enclosure Type Rating
None (open style)
Power Consumption
3.6 A @5V dc max
Power Dissipation
18.9 W max
Isolation
(continuous voltage rating)
50V Basic Insulation between communication ports and between communication ports
and backplane
Tested to withstand 500V rms for 60 s
Wire Size
Ethernet: 802.3 compliant shielded or unshielded twisted pair
Remote I/O: 1770-CD cable
Serial Ports: Belden 8342 or equivalent
Wiring Category
(1)
2 - on communications ports
Replacement Battery
1770-XYC
North American Temp Code
T4A
Specifications continued on next page
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1.