Publication 1785-IN063B-EN-P - January 2006

22 Ethernet PLC-5 Programmable Controllers

Troubleshoot the Controller Communication Channels

Indicator

Color

Channel Mode

Description

Probable
Cause

Recommended
Action

A or B

Green

(steady)

Remote I/O
Scanner

Active Remote I/O link, all
adapter modules are
present and not faulted

Normal
operation

No action required

Remote I/O
Adapter

Communicating with
scanner

DH+

Controller is transmitting
or receiving on DH+ link

Green

(blinking

rapidly or
slowly)

Remote I/O
Scanner

At least one adapter is
faulted or has failed

Power off at
remote rack

Cable broken

Restore power to the
rack

Repair cable

DH+

No other nodes on network

Red

(steady)

Remote I/O
Scanner

Remote I/O
Adapter

DH+

Hardware fault

Hardware error

Turn power off, then
on.

Check that the
software
configurations match
the hardware set-up.

Replace the controller.

Red

(blinking

rapidly or
slowly)

Remote I/O
Scanner

Faulted adapters detected

Cable not
connected or is
broken

Power off at
remote racks

Repair cable

Restore power to racks

DH+

Bad communication on
DH+

Duplicate node
detected

Correct station address

Off

Remote I/O
Scanner

Remote I/O
Adapter

DH+

Channel offline

Channel is not
being used

Place channel online if
needed