Troubleshoot the controller communication channels – Rockwell Automation 1785-Lx0E Ethernet PLC-5 Programmable Controllers Installation Instructions User Manual
Page 22
Publication 1785-IN063B-EN-P - January 2006
22 Ethernet PLC-5 Programmable Controllers
Troubleshoot the Controller Communication Channels
Indicator
Color
Channel Mode
Description
Probable
Cause
Recommended
Action
A or B
Green
(steady)
Remote I/O
Scanner
Active Remote I/O link, all
adapter modules are
present and not faulted
Normal
operation
No action required
Remote I/O
Adapter
Communicating with
scanner
DH+
Controller is transmitting
or receiving on DH+ link
Green
(blinking
rapidly or
slowly)
Remote I/O
Scanner
At least one adapter is
faulted or has failed
Power off at
remote rack
Cable broken
Restore power to the
rack
Repair cable
DH+
No other nodes on network
Red
(steady)
Remote I/O
Scanner
Remote I/O
Adapter
DH+
Hardware fault
Hardware error
Turn power off, then
on.
Check that the
software
configurations match
the hardware set-up.
Replace the controller.
Red
(blinking
rapidly or
slowly)
Remote I/O
Scanner
Faulted adapters detected
Cable not
connected or is
broken
Power off at
remote racks
Repair cable
Restore power to racks
DH+
Bad communication on
DH+
Duplicate node
detected
Correct station address
Off
Remote I/O
Scanner
Remote I/O
Adapter
DH+
Channel offline
Channel is not
being used
Place channel online if
needed
A
A
B
43920