beautypg.com

A - module specifications, Electrical specifications, Physical specifications – Rockwell Automation 1746-QV,D17466.18 OPEN-LOOP VELOCITY CONTL User Manual

Page 27: Environmental specifications, Module specifications, Appendix

background image

Appendix

A

Publication 1746-6.18 April 1998

Module Specifications

This appendix lists the specifications for the
1746-QV Open-loop Velocity Control Module.

Power Requirements

215 mA at 5V dc (from backplane)
400 mA at +15V dc and 295 mA at –15V dc
(from independent PS, typical but LDT dependent)

I/O Chassis Location

Any I/O-chassis slot except slot 0

Isolation

1500V ac optical isolation
between LDT input and backplane

LDT Inputs

"Interrogate

"Gate

"15V dc PS
PS Common
Shield/Frame

Compatible LDT Input Devices

Linear Displacement Transducer such as:
Balluff BTL-2-L2 or -M2
Gemco Quick-Stick II
Santest GYRP or GYRG
Temposonics II with DPM or RPM

Module Range
and Resolution

160 inches

"0.01 inch

Analog Output

0-10V dc @ 250 mA or
–10 to +10V dc @ 250 mA

Accuracy of Voltage Output

Within

"1% of its programmed value

Module Update Time

2 ms

LED Indicators

Run

ON

Profile running, Output active

(green):

Flashing

Output at 0V dc

Fault OFF

Module

OK

(red):

Flashing

LDT fault

ON

Module fault

Module ID Code

13115

Maximum Wire Size

Two 18 AWG wires per terminal on terminal block

Operating Temperature

0

°

C to 60

°

C (32

°

F to 140

°

F)

Storage Temperature

–40

°

C to

+

85

°

C (–40

°

F to

+

185

°

F)

Relative Humidity

5% to 95% (without condensation)

Agency Certification
(when marked on
product or package)

CE marked for all applicable directives

Electrical Specifications

Physical Specifications

Environmental Specifications