beautypg.com

Rockwell Automation 1757-FFLD4 Foundation Fieldbus Linking Device Installation Instructions User Manual

Page 13

background image

Foundation Fieldbus Linking Device 13

Publication

1757-IN021E-EN-P - August 2009

3. Complete

step 1

and

step 2

for all H1 cables.

4. Insert the RTB into the corresponding socket.

H1 Terminal Block Layout (catalog number 1757-FFLD4 shown)

Power and Grounding

1. Connect the chassis ground to connector 1 - CHASSIS GND.

2. Connect the 24V common to connector 2 - DC GND.

3. Connect the +24V DC input power to connector 3 - 24V DC (

+

20%).

4. Apply power to the linking device.

IMPORTANT

You must use a power conditioner between your fieldbus power supply and
the devices on the fieldbus network. For more information, see the
F

OUNDATION

Fieldbus specifications at

http://www.fieldbus.org

,

publication

AG-140

Do not exceed 10 m (32.8 ft) total wiring length on the 24V DC power
connection.

H1-1

+ -

+ -

+ -

+ -

+ -

+ -

+ -

+ -

H1-2

H1-3

H1-4

1

CHASSIS GND

2

DC Gnd

3

24V DC (+20%)

43576

This manual is related to the following products: