Rockwell Automation 1784-KTCX15 INSTL INSTR CONTROLNET COMM. User Manual
Page 6

6
ControlNet Communication Interface Card
Publication 1784-5.33 – September 1997
Selecting the Base Memory Address Location
The host computer and the card exchange data via a dual-port interface. The
dual-port interface is 16 Kbytes long and it begins at the specified base memory
address location.
The card comes set to memory address D000:0000. You may find that this
selected memory address has been allocated to other interface cards or expansion
memory cards you have installed in your computer system. If this occurs,
change the switch settings to an available memory address.
To select a new base memory address:
1. Pick an available address from the ROM I/O adapters area of the host
computer’s memory. Be sure to choose a block that is 16 Kbytes long.
2. Use Worksheet A to select a new memory address for the card.
3. Use Worksheet B to determine the proper switch settings.
Follow this guide to properly set your switches.
up (1)
down (0)
1 2
1 2 3 4
MSB
LSB
Front View
up (1)
down (0)
Side View
Front View
S2
S1
4. Fill in Worksheet C after you’ve determined your switch settings.
5. Follow the instructions that begin on page 11.
ControlNet Communication Interface Card
31
Publication 1784-5.33 – September 1997
Specifications
The operating parameters describe the environment within the KTCX15 slot.
Refer to the documentation for your computer for environmental requirements.
The card should not exceed those specifications.
General Specifications
Characteristic
Value
Power
Requirements
5V dc, 640mA Maximum
Conductor
Category 2
Environmental Specifications
Operating
Nonoperating
Slot Temperature
0 to 50
°
C (32 to 122
°
F)
– 40 to 85
°
C (– 40 to 185
°
F)
Humidity
5 to 95% without condensation
5 to 95% without condensation
Vibration
10 to 150 Hz, constant .012 in
displacement
10 to 150 Hz, constant 2.0G
acceleration
not applicable
Shock
30G peak/11 ms
50G peak/11 ms
Agency Certification
(when product or packaging is marked)
Class 1, Division 2
Groups A, B, C, D
П
П
П
П
ПП
ПП
П
П
marked for all applicable directives