Rockwell Automation 1608M MegaDySC User Manual, 800 - 2400 A User Manual
Page 37
37
Rockwell Automation Publication 1608M-UM002A-EN-P - September 2013
Chapter 7
Maintenance
31
CONFIG
Configuration Alert
Call Service
Inverter
Controller configuration has changed.
Call service.
32
CNTRL_MEM
Controller Memory Busy
Auto-Resetting
Inverter
Controller is loading new data into Flash memory.
No action needed.
33
UNBALANCE
Start-Up Test: DC Bus Unbalance
Call Service
Inverter
Positive and negative halves of the DC bus did not charge equally during power up.
Call service.
34
AC_V_CHK
Start-Up Test: AC Voltage Check
Call Service
Inverter
Output voltage was detected out of tolerance during the start-up test.
Call service.
35
ROLL_CALL
Start-Up Test: Controller Roll Call Timeout
Call Service
Unit
Controller communication problem detected during start-up test.
Call service.
36
COM_VER
Start-Up Test: Communication Compatibility
Mismatch
Call Service
Unit
Firmware communication compatibility problem detected during start-up test.
Call service.
37
CNFG_TO
Start-Up Test: Controller Configuration Timeout
Call Service
Unit
Controller communication problem detected during start-up test.
Call service.
38
CNFG_ERR
Start-Up Test: Controller Configuration
Mismatch
Call Service
Unit
Controller firmware configuration problem detected during start-up test.
Call service.
39
FIRM_TO
Start-Up Test: Controller Firmware Check
Timeout
Call Service
Unit
Controller communication problem detected during start-up test.
Call service.
40
FIvRM_DIFF
Start-Up Test: Controller Firmware Revision
Mismatch
Call Service
Unit
Controller firmware revision mismatch detected during start-up test.
Call service.
41
SRL_TO
Start-Up Test: Controller Serial Number Check
Timeout
Call Service
Unit
Controller communication problem detected during start-up test.
Call service.
42
SRL_DIFF
Start-Up Test: Serial Number Mismatch
Informational
Unit
Controller serial number mismatch detected during start-up test.
No action needed.
44
T_INV_TO
Inverter Test Timeout
Call Service
Unit
Phase control board failed to respond to Comm board's Inverter test.
Call service.
46
DOOR_OPEN
DySC Cabinet Door Open
Manual Reset
Unit
DySC door was opened. Mechanical bypass commanded.
Close door. Manually reset DySC.
47
CRIT_OT
Critical Over-Temperature
Manual Reset
Unit
Internal DySC temperature exceeded maximum rating. Mechanical bypass
commanded.
Verify ambient temperature is within DySC
specification. Check for damaged fans.
Check for dirty or obstructed air filters.
Manually reset DySC.
48
FUSE_OPEN
Fuse Open
Call Service
Unit
One of the DySC fuses was detected open. Mechanical bypass commanded.
Call service.
49
OPEN_SCR_A
Open SCR Phase A
Call Service
Static Switch
The SCR on the phase A module was detected open.
Call service.
50
OPEN_SCR_B
Open SCR Phase B
Call Service
Static Switch
The SCR on the phase B module was detected open.
Call service.
51
OPEN_SCR_C
Open SCR Phase C
Call Service
Static Switch
The SCR on the phase C module was detected open.
Call service.
52
EXT_MB
External Mechanical Bypass Command
Manual Reset
Unit
The DySC was externally commanded to transfer to mechanical bypass.
Manually reset DySC.
53
DYN_BRAKE
Dynamic Brake Error
Call Service
Unit
A problem was detected with the DySC dynamic brake controller.
Call service.
54
SLAVE_OL
Critical Slave Cabinet Overload
User Attention
Unit
Slave cabinet current exceeded maximum rating. Mechanical bypass commanded.
Verify proper current sharing among slave
cabinets. Verify proper DySC application.
Call service.
55
MSTR_A_UV
Phase A Master Controller Under-Voltage
Call Service
Unit
Phase A master controller power supply failure. Mechanical bypass commanded.
Call service.
56
MSTR_B_UV
Phase B Master Controller Under-Voltage
Call Service
Unit
Phase B master controller power supply failure. Mechanical bypass commanded.
Call service.
57
MSTR_C_UV
Phase C Master Controller Under-Voltage
Call Service
Unit
Phase C master controller power supply failure. Mechanical bypass commanded.
Call service.
58
PLC_ERR
Programmable Logic Controller Error
Call Service
PLC
PLC error detected.
Call service.
Event
Code
Code Name
Full Name
Severity
Area
Event Description
Event Resolution