Chapter 7

Maintenance

Table 6 - System Event Table

Event

Code

Code Name

Full Name

Severity

Area

Event Description

Event Resolution

1

POWER_ON

DySC Power On

Informational

Unit

Power re-applied to the DySC.

No action needed.

4

T_FAN_ST

Fan Test Start

Informational

Unit

Start acknowledgment of DySC fan test.

No action needed.

5

T_IN_ST_1

Inverter Test (.5 cycles) Start

Informational

Unit

Start acknowledgment of DySC 0.5 cycle inverter test.

No action needed.

6

T_IN_ST_2

Inverter Test (3 cycles) Start

Informational

Unit

Start acknowledgment of DySC 3 cycle inverter test.

No action needed.

7

T_IN_ST_3

Inverter Test (5.5 seconds) Start

Informational

Unit

Start acknowledgment of DySC 5.5 second inverter test.

No action needed.

9

EXTERNAL

External Inhibit

Auto-Resetting

Inverter

Controller is inhibited by another phase controller.

Review event details from other phase
controllers.

10

EXT_SLAVE

External Slave Cabinet Inhibit

Auto-Resetting

Inverter

Master controller is inhibited by another phase master controller.

Review event details from slave controllers.

11

RUN_TO

Inverter Run Timeout

Auto-Resetting

Inverter

DySC inverter had a total cumulative runtime of more than rated.

No action needed.

12

LIM_CYCLE

Inverter Limit Cycle Timeout

Auto-Resetting

Inverter

Power was re-applied more than once within a 58 second period.

No action needed.

13

STAT_OT

Static Switch Over-Temperature

User Attention

Static Switch

Static switch heatsink temperature was greater than maximum rating.

Verify ambient temperature is within DySC
specification. Check for damaged fans.
Check for dirty or obstructed air filters.

14

OVERLOAD

Overload

User Attention

Unit

Inverter inhibited because load current exceeded maximum rating.

Reduce load. In parallel DySC systems, verify
proper current sharing among slave
cabinets.

15

DC_OV

DC Bus Over-Voltage

User Attention

Inverter

Positive or negative half of DC bus voltage exceeded maximum rating.

Verify line voltage is within ratings. Verify
proper DySC application. Call service.

16

CNTRL_UV

Controller Power Under-Voltage

User Attention

Inverter

DySC control power supply is out of tolerance.

Verify DySC is online and line voltage is
within ratings. Call service.

17

OUTPUT_UV

Output Under-Voltage

User Attention

Inverter

DySC output voltage was less than 80% of nominal during sag correction. Sag
condition likely outside of DySC specification.

Verify line voltage is within ratings. Verify
proper DySC application.

18

INV_OC

Inverter Over-Current

User Attention

Inverter

Inverter current exceeded maximum rating during sag correction.

Verify load current is within ratings. Verify
mechanical bypass circuit breaker CBB is
open. Verify proper DySC application.

19

DC_UV

DC Bus Under-Voltage

User Attention

Inverter

DC bus voltage below operational range.

Verify line voltage is within ratings. Call
service.

20

OUTPUT_OV

Output Over-Voltage

Call Service

Inverter

DySC output voltage was greater than 115% of nominal during sag correction.

Call service.

22

IGBT

IGBT Pack

User Attention

Inverter

IGBT pack reported error. Possible sag condition outside of DySC specification.

Verify line voltage is within ratings. Verify
proper DySC application. Call Service.

24

GATE_ERR

Gate Command Error

Call Service

Static Switch

Master/slave gate command error.

Call service.

25

SYNC_ERR

Line Synchronization Error

Call Service

Inverter

Inverter not synchronized to line when sag detected.

Call service.

26

SLAVE_1

Slave Cabinet 1 Inhibit

Auto-Resetting

Inverter

Master controller inhibited by slave controller.

Review event details from slave controllers.

27

SLAVE_2

Slave Cabinet 2 Inhibit

Auto-Resetting

Inverter

Master controller inhibited by slave controller.

Review event details from slave controllers.

28

CR_SLV_1

Critical Slave Cabinet 1 Inhibit

Manual Reset

Static Switch

Master controller inhibited by slave controller. Mechanical bypass commanded.

Review event details from slave controllers.
Call service.

29

CR_SLV_2

Critical Slave Cabinet 2 Inhibit

Manual Reset

Static Switch

Master controller inhibited by slave controller. Mechanical bypass commanded.

Review event details from slave controllers.
Call service.

30

CRIT_OL

Critical Static Switch Overload

User Attention

Static Switch

Slave cabinet current exceeded maximum rating. Mechanical bypass commanded.

Verify proper current sharing among slave
cabinets. Verify proper DySC application.
Call service.