Table 6 - system event table, Table 6 on – Rockwell Automation 1608M MegaDySC User Manual, 800 - 2400 A User Manual
Page 36
36
Rockwell Automation Publication 1608M-UM002A-EN-P - September 2013
Chapter 7
Maintenance
Table 6 - System Event Table
Event
Code
Code Name
Full Name
Severity
Area
Event Description
Event Resolution
1
POWER_ON
DySC Power On
Informational
Unit
Power re-applied to the DySC.
No action needed.
4
T_FAN_ST
Fan Test Start
Informational
Unit
Start acknowledgment of DySC fan test.
No action needed.
5
T_IN_ST_1
Inverter Test (.5 cycles) Start
Informational
Unit
Start acknowledgment of DySC 0.5 cycle inverter test.
No action needed.
6
T_IN_ST_2
Inverter Test (3 cycles) Start
Informational
Unit
Start acknowledgment of DySC 3 cycle inverter test.
No action needed.
7
T_IN_ST_3
Inverter Test (5.5 seconds) Start
Informational
Unit
Start acknowledgment of DySC 5.5 second inverter test.
No action needed.
9
EXTERNAL
External Inhibit
Auto-Resetting
Inverter
Controller is inhibited by another phase controller.
Review event details from other phase
controllers.
10
EXT_SLAVE
External Slave Cabinet Inhibit
Auto-Resetting
Inverter
Master controller is inhibited by another phase master controller.
Review event details from slave controllers.
11
RUN_TO
Inverter Run Timeout
Auto-Resetting
Inverter
DySC inverter had a total cumulative runtime of more than rated.
No action needed.
12
LIM_CYCLE
Inverter Limit Cycle Timeout
Auto-Resetting
Inverter
Power was re-applied more than once within a 58 second period.
No action needed.
13
STAT_OT
Static Switch Over-Temperature
User Attention
Static Switch
Static switch heatsink temperature was greater than maximum rating.
Verify ambient temperature is within DySC
specification. Check for damaged fans.
Check for dirty or obstructed air filters.
14
OVERLOAD
Overload
User Attention
Unit
Inverter inhibited because load current exceeded maximum rating.
Reduce load. In parallel DySC systems, verify
proper current sharing among slave
cabinets.
15
DC_OV
DC Bus Over-Voltage
User Attention
Inverter
Positive or negative half of DC bus voltage exceeded maximum rating.
Verify line voltage is within ratings. Verify
proper DySC application. Call service.
16
CNTRL_UV
Controller Power Under-Voltage
User Attention
Inverter
DySC control power supply is out of tolerance.
Verify DySC is online and line voltage is
within ratings. Call service.
17
OUTPUT_UV
Output Under-Voltage
User Attention
Inverter
DySC output voltage was less than 80% of nominal during sag correction. Sag
condition likely outside of DySC specification.
Verify line voltage is within ratings. Verify
proper DySC application.
18
INV_OC
Inverter Over-Current
User Attention
Inverter
Inverter current exceeded maximum rating during sag correction.
Verify load current is within ratings. Verify
mechanical bypass circuit breaker CBB is
open. Verify proper DySC application.
19
DC_UV
DC Bus Under-Voltage
User Attention
Inverter
DC bus voltage below operational range.
Verify line voltage is within ratings. Call
service.
20
OUTPUT_OV
Output Over-Voltage
Call Service
Inverter
DySC output voltage was greater than 115% of nominal during sag correction.
Call service.
22
IGBT
IGBT Pack
User Attention
Inverter
IGBT pack reported error. Possible sag condition outside of DySC specification.
Verify line voltage is within ratings. Verify
proper DySC application. Call Service.
24
GATE_ERR
Gate Command Error
Call Service
Static Switch
Master/slave gate command error.
Call service.
25
SYNC_ERR
Line Synchronization Error
Call Service
Inverter
Inverter not synchronized to line when sag detected.
Call service.
26
SLAVE_1
Slave Cabinet 1 Inhibit
Auto-Resetting
Inverter
Master controller inhibited by slave controller.
Review event details from slave controllers.
27
SLAVE_2
Slave Cabinet 2 Inhibit
Auto-Resetting
Inverter
Master controller inhibited by slave controller.
Review event details from slave controllers.
28
CR_SLV_1
Critical Slave Cabinet 1 Inhibit
Manual Reset
Static Switch
Master controller inhibited by slave controller. Mechanical bypass commanded.
Review event details from slave controllers.
Call service.
29
CR_SLV_2
Critical Slave Cabinet 2 Inhibit
Manual Reset
Static Switch
Master controller inhibited by slave controller. Mechanical bypass commanded.
Review event details from slave controllers.
Call service.
30
CRIT_OL
Critical Static Switch Overload
User Attention
Static Switch
Slave cabinet current exceeded maximum rating. Mechanical bypass commanded.
Verify proper current sharing among slave
cabinets. Verify proper DySC application.
Call service.