Installation
Chapter 2
connected to the bus bar terminals labeled L1, L2, L3 and the protected load is
connected to the bus bar terminals labeled X1, X2, X3.
Figure 4 - Bus Bar Details for Utility Input and Load Output Terminations
MegaDySC System Interconnections Checklist
The following list of checks is provided for reference only. Interconnections must
be completed by factory-trained and authorized installation personnel.
•
Connect each MegaDySC Unit's ground cable to the ground bus in ABP
Switchboard.
•
Connect line side cables from each MegaDySC Unit to the respective line
input bus in the ABP Switchboard labeled L1, L2 and L3 respectively.
•
Connect load side cables from each MegaDySC Unit to the respective load
output bus in the ABP Switchboard labeled X1, X2 and X3 respectively.
Note: It is critical to match the phases on each MegaDySC section.
•
Plug the 4 duplex fiber optic cables into the appropriate transceiver found
on the control PC boards of each MegaDySC Unit's phase inverter
module.
•
Plug in the control wire harnesses that interconnect the enclosures at the
bottom of each unit.
•
Check wiring for correct source and destination locations against
approved drawings.
•
Check all electrical terminations for proper torque.
•
Refer start-up and commissioning to factory-trained and authorized
service personnel.
Right-side cut-away view of Switchboard
Detail:
Typical bus bar hole pattern
OUTPUT to loads
UTILITY INPUT
NEUTRAL
Top Entry Area