Chapter 7, Maintenance, Preventative maintenance – Rockwell Automation 1608M MegaDySC User Manual, 800 - 2400 A User Manual
Page 35: Monthly checks, 6 month checks, Ch 7 - maintenance, Monthly checks 3-6 month checks, Chapter
Rockwell Automation Publication 1608M-UM002A-EN-P - September 2013
35
Chapter
7
Maintenance
Preventative Maintenance
The MegaDySC requires very little preventative maintenance. The MegaDySC
should be checked periodically for proper air flow and status indicator operation.
Monthly Checks
•
Ensure the touch screen display is working and no active events are
displayed.
•
Check that the Automatic Bypass switchboard is in the MegaDySC
Normal mode.
•
Update system time, if needed, see
.
•
Clean the display screen if needed. See page
.
•
Ensure air intake and exhaust filters are not covered or obstructed.
3-6 Month Checks
•
Check air filters and clean when necessary.
–
Air filters for the MegaDySC will require periodic cleaning, with the
frequency depending on the environment.
–
Filters are located on the doors of each MegaDySC and ER cabinet, and
can be accessed with the doors closed.
–
The MegaDySC need not have power removed for this operation.
–
Remove the grill covers by unscrewing the knurled nuts; the washable
foam filter pads are behind the grill cover.
–
Replace or gently wash the foam filter pads as needed with a light non-
abrasive soap and water mixture. Towel-dry; do not wring-out.
–
Place the filter and grill cover back into their location and re-install the
knurled nuts until finger tight.
–
Replace filters if damaged.
–
Consult Rockwell Automation technical support for replacement
filters.
–
Replacement filters must be no more restrictive to air flow than the
original equipment filters.
•
Check fan for proper operation.
–
Refer to the Hardware Service Manual for fan test instructions.