Product Description
1-5
1503-UM052D-EN-P – June 2013
Specifications
Mounting and Connections
The IntelliVAC
control modules are mounted using two (2) screws (see
Figure 1.3). They are typically located in the low voltage control panel
of the medium voltage controller (Bulletin 1500/1900 controllers, in
the case of Rockwell Automation).
IntelliVAC is interfaced to the Bulletin 1502 vacuum contactors using
a “quick” connector, located at the module, a wire harness and “quick”
connector at the contactor. Control power and other control circuit
connections are similarly achieved with “quick” connectors.
Configuration
IntelliVAC
is easily configured for a wide variety of medium voltage
motor and feeder control applications. It is configured using DIP
switches, located within the enclosure (front side). Please refer to
Chapter 4 for information.
Bulletin 1500/1900 controllers are shipped with IntelliVAC pre-
configured for the required application. Please refer to the documents
provided with the order.
Firmware
IntelliVAC
has firmware stored in flash EEPROM; therefore, this may
be updated in the field (if necessary). The IntelliVAC
board firmware
is updated using the mini-DIN connector, which is accessible inside the
enclosure.
The firmware version supplied with the module is displayed on top of
the DIP switches (see Figure 4.1).
Series C modules use only version 2.003 application firmware. This
firmware is also compatible with the Series A and B modules. Series D
modules use only version 3.001 or 3.002 application firmware. This
firmware is not compatible with any other Series Letter modules.
Refer to Chapter 6 for part numbers of the various series of modules.
The Series Letter of the module is printed on the label on the cover of
the module, beside the part number.