Rockwell Automation 1503 IntelliVAC Contactor Control Module - Series C and later User Manual
Page 10

1-6
Product Description
1503-UM052D-EN-P – June 2013
Table 1.A – Electrical Ratings
Main Input Voltage
(L1 to L2/N)
AC – 110 to 240 V rms, +10/-15%, 47 to 63 Hz
DC – 110 to 250 V, +10/-15%
Main Input Current
(L1 to L2/N)
Description
Contactor Ratings
(Amps)
Control Voltage
(AC or DC)
AC Rating
DC Rating
Inrush Current
400/800
120/240
25 A peak (1/2
cycle)
25 A peak
Idle Current
(Maximum without contactor coil
energized)
400/800
120/240
125 mA
35 mA
Hold Current ⊄ (maximum)
400/800
120/240
300 mA
100 mA
Close Current ⊄
(0.2 sec)
400
120
4.6 A
3.6 A
240
3.4 A
3.3 A
800
120
11.3 A
4.8 A
240
8.9 A
4.5 A
Trip Current (latch) ⊄
(0.2 sec)
400
120
7.0 A
3.7 A
240
3.6 A
2.0 A
800
120
7.0 A
3.3 A
240
4.3 A
1.9 A
Command Inputs
⊇ ⊂
AC – 100 to 240 V rms
DC – 50 to 250 V
Maximum on state current for open or close command:
9mA
AC
@ 250 V AC, 60Hz, T
A
= 60°C
9mA
DC
@ 250 V DC, T
A
= 60°C
Minimum on state current for open or close command:
2mA
AC
@ 100 V AC, 60Hz, T
A
= 60°C
1.2 mA @ 50 V DC, T
A
= 60°C
Maximum off state current for open or close command:
700 µA @ 20 V AC, 60 Hz, T
A
= 60°C
900 µA @ 30 V DC, T
A
= 60°C
Status Output Contacts
AC – 250 V rms, 5 A, R load; 2 A (reactive), PF = 0.4
DC – 30 V, 5 A, R load; 2 A (reactive), L/R = 7 ms
Standards and Approvals
CE, cULus, CSA, IEC pending
⊇
T
A =
Ambient Temperature
⊄
Includes idle current.
⊂
Ensure compatibility of IntelliVAC input ratings with those of circuit components activating these inputs.
Consider means of isolating/loading these signals, as required (using interposing relays or load resistors.)
Consult factory for assistance, if needed. The Series C and D IntelliVACs are compatible with most PLC outputs,
and have been verified with Rockwell Automation OA type 120V triac outputs. See Chapter 3, Wiring Guidelines.