Description (cont.), Intellivac features, Figure 1.1 – intellivac contactor control module – Rockwell Automation 1503 IntelliVAC Contactor Control Module - Series C and later User Manual
Page 6: Figure 1.2 – intellivac block diagram
1-2
Product Description
1503-UM052D-EN-P – June 2013
Figure 1.1 – IntelliVAC Contactor Control Module
Description (cont.)
Micro Controller
C
ont
ac
tor
C
oi
l(s
) I
nt
er
fac
e
Configuration
Inputs
(DIP
switches)
Command
Inputs
Current
Regulator
IGBT Coil
Switching
CC
Input
Power
Conditioning
C
oi
l C
ur
rent
T
rans
duc
er
Vacuum Contactor
Close Coil
Vacuum Contactor
Trip Coil
Supply
Voltage
110-240
VAC
or
110-250
VDC
Close
Signal
Open
Signal
Vacuum Contactor
Auxiliary
C
C
External
Capacitor
(Optional)
Module
Status
Contactor
Status
A
u
x.
F
eedbac
k
S
ta
tu
s
Ou
tp
u
ts
c
Altitude
Select
Drop-Out
Select
TDUV
Time
Select
Contactor
Select
c
c
c
c
c
c
c
c
c
c
c
Flash EEPROM
Interface
Coil
Power
Supply
Control
Power
Supply
Power Up
Safety
c
c
c
Figure 1.2 – IntelliVAC Block Diagram
IntelliVAC Features
A wide range of supply voltage (110 – 240 V AC 50/60 Hz, 110 -
250 V DC) allows implementation in multiple applications
Consistent vacuum contactor pick-up time (at a given supply
voltage) ensures repeatable performance
Selectable vacuum contactor drop-out time improves coordination
with upstream power fuses
Electronic altitude compensation (400 A only) eliminates
mechanical compensation required for altitudes above 1,000
meters (800 A contactors include a user-friendly altitude
adjustment)