Interface connections – Rockwell Automation 1503 IntelliVAC Contactor Control Module - Series C and later User Manual
Page 23
![background image](/manuals/578845/23/background.png)
3-10
Installation and Wiring
1503-UM052D-EN-P – June 2013
Interface Connections
All other control interface connections are made at a twelve-pole
connector located on the top of the module. Refer to Figure 3.5 and
Table 3.B for connections (and Table 1.A for electrical ratings).
Refer to the
Wiring Guidelines section in this chapter for guidance in
making connections to the control circuit.
CONTACTOR INTERFACE
11 12
8
9
10
5
6
7
2
3
4
1
EX. CAP.
Figure 3.5 – Top side connections
Table 3.B – Terminal Assignments for IntelliVAC Interface Connections
Terminal No.
Terminal Designation
Description
1
External capacitor (negative)
Power connection for TDUV or capacitor trip options
only
2
External capacitor (positive)
3
Latch trip coil (common)
Output for mechanical latch contactor trip coil
4
Latch trip coil
5
Close coil (common)
Output to close coil of electrically held &
mechanical latch contactors
6
Close coil
7
Open / Jog command
Input to open a mechanical latch contactor or jog
an electrically held contactor (mutually exclusive)
8
Open / Jog command (common)
9
Close command
Input to initiate the closure of electrically held and
mechanical latch contactors
10
Close command (common)
11
Contactor auxiliary contact
Input to indicate the state of the contactor
(typically wired to a normally closed auxiliary
contact)
12
Contactor auxiliary contact
Refer to Table 1.A for electrical ratings.
No connection required if option is not used.
Ensure compatibility of IntelliVAC input ratings with those of circuit components activating these inputs. Consider means of
isolating/loading these signals, as required (using interposing relays or load resistors). Consult factory for assistance, if needed. The
Series C and D IntelliVACs are compatible with most PLC outputs, and have been verified with Rockwell Automation OA type 120V
triac outputs. See Wiring Guidelines.
For electrically held contactor, this command will energize the close coil output (CCO).
For mechanically held contactor, this command will energize the trip coil output (TCO).