1 Output Voltage
0
200% Rated Drive Output Voltage
Read Only
2 % Output Curr
0%
200% Rated Drive Output Current
Read Only
3 % Output Power
200% Drive Rated Output Power
+200% Drive Rated Output Power
Read Only
4 Last Fault
None
None
Read Only
5 Freq Select 1
Use Last
Adapter 1
Analog In 0
Analog In 1
Analog In 2
Pulse Ref
MOP
Adapter 1
Adapter 2
Adapter 3
Adapter 4
Adapter 5
Adapter 6
Preset 1
Preset 2
Preset 3
Preset 4
Preset 5
Preset 6
Preset 7
Encoder
6 Freq Select 2
Use Last
Preset 1
Analog In 0
Analog In 1
Analog In 2
Pulse Ref
MOP
Adapter 1
Adapter 2
Adapter 3
Adapter 4
Adapter 5
Adapter 6
Preset 1
Preset 2
Preset 3
Preset 4
Preset 5
Preset 6
Preset 7
7 Accel Time 1
0.0 Sec
3600.0 Sec
10.0 Sec
8 Decel Time 1
0.0 Sec
3600.0 Sec
10.0 Sec
9 Control Select
Economize
Sens Vector
Sens Vector
Fixed Boost
Full Custom
10 Stop Select 1
Coast
Coast
DC Brake
Ramp
S-Curve
Ramp to Hold
11 Bus Limit En
Disabled
Disabled
Enabled
12 DC Hold Time
0.0 Sec
90.0 Sec
0.0 Sec
13 DC Hold Level
0%
150%
0%
14 Run On Power Up
Disabled
Disabled
Enabled
15 Reset/Run Time
0.5 Sec
30.0 Sec
1.0 Sec
16 Minimum Freq
0 Hz
120 Hz
0 Hz
17 Base Frequency
25 Hz
400 Hz
60 Hz
18 Base Voltage
25% of Drive Rated Voltage
120% of Drive Rated Voltage
Drive Rated Volts
19 Maximum Freq
10 Hz
400 Hz
60 Hz
20 Maximum Voltage
25% of Drive Rated Voltage
120% of Drive Rated Voltage
Drive Rated Volts
21 Spare
22 MOP Increment
0 Hz/Sec
(78% of [Maximum Freq])/Sec
1.1 Hz/Sec
23 Output Power
-200% Rated Drive Output Power
+200% Rated Drive Output Power
Read Only
24 Jog Frequency
0.0 Hz
400.0 Hz
10.0 Hz
25 Anlg Out 0 Sel
Frequency
Frequency
Current
Torque
Power
Voltage
% Motor OL
% Drive OL
Encoder
Speed Error
PI Reference
PI Feedback
PI Error
PI Output
26 Stop Mode Used
Coast
Coast
DC Brake
Ramp
S Curve
Ramp to Hold
27 Preset Freq 1
0.0 Hz
400.0 Hz
0.0 Hz
28 Preset Freq 2
0.0 Hz
400.0 Hz
0.0 Hz
29 Preset Freq 3
0.0 Hz
400.0 Hz
0.0 Hz
30 Accel Time 2
0.0 Sec
3600.0 Sec
10.0 Sec
31 Decel Time 2
0.0 Sec
3600.0 Sec
10.0 Sec
32 Skip Freq 1
0 Hz
400 Hz
400 Hz
33 Skip Freq 2
0 Hz
400 Hz
400 Hz
34 Skip Freq 3
0 Hz
400 Hz
400 Hz
35 Skip Freq Band
0 Hz
15 Hz
0 Hz
36 Current Limit
20% of [Rated Amps]
300% of [Rated Amps]
150%
37 Overload Mode
Max Derate
No Derate
Min Derate
No Derate