Rockwell Automation 1336 3-20HP FRN 1.01-3.01 User Manual
Page 34
Specifications
Chapter 4
4-7
Table 4.3 -- B003ĆB200 Output Current and kVA
Internal
Chassis
Component
Heatsink
Heat
Heat
Total
Minimum
Drive
kVA Out
kVA Out
kVA Out
Dissipation
Dissipation
Dissipation
CFM
Amps Out
Rating
380V AC
415V AC
460V AC
(BTU/hour) n
(BTU/hour) n
(BTU/hour) n
Required n
6.0
B003
3.9
4.3
4.8
136
239
375
15
9.6
B005
6.3
6.9
7.6
171
307
477
25
13.0
B007
8.6
9.3
10.4
273
512
784
40
17.0
B010
11.2
12.2
13.5
341
682
1023
53
25.0
B015
16.5
18.0
20.0
443
1023
1466
76
33.0
B020
22.0
24.0
26.0
477
1364
1841
95
41.0
B025
27.0
29.0
33.0
614
1705
2319
120
48.0
B030
32.0
35.0
38.0
716
2046
2762
142
60.0
B040
39.0
43.0
48.0
938
2438
3376
175
75.0
B050
49.0
54.0
60.0
1125
2847
3973
205
120.0
B075
79.0
86.0
96.0
1705
5115
6820
352
150.0
B100
99.0
108.0
120.0
2046
7502
9548
492
180.0
B125
118.0
129.0
143.0
2387
8184
10571
545
218.0
B150
143.0
157.0
174.0
2728
10912
13640
703
290.0
B200
191.0
208.0
231.0
3069
13981
17050
880
Table 4.4 -- C003ĆC200 Output Current and kVA
Internal
Chassis
Component
Heatsink
Heat
Heat
Total
Minimum
Drive
kVA Out
kVA Out
kVA Out
Dissipation
Dissipation
Dissipation
CFM
Amps Out
Rating
500V AC
575V AC
600V AC
(BTU/hour) n
(BTU/hour) n
(BTU/hour) n
Required n
4.3
C003
3.7
4.3
4.3
136
239
375
15
6.7
C005
5.8
6.7
6.7
171
307
477
25
9.9
C007
8.6
9.9
9.9
273
444
717
40
12.1
C010
10.5
12.1
12.1
341
512
853
45
19.0
C015
16.5
18.9
18.9
443
853
1296
60
24.0
C020
20.8
23.9
23.9
477
1023
1500
80
30.0
C025
26.0
29.9
29.9
614
1364
1978
105
35.0
C030
30.3
34.9
34.9
716
1535
2251
115
45.0
C040
39.0
44.8
44.8
938
1876
2814
145
57.0
C050
49.4
56.8
56.8
1125
2217
3342
175
85.0
C075
73.6
84.7
84.7
1705
4433
6138
320
109.0
C100
94.4
108.6
108.6
2046
5797
7843
405
138.0
C125
119.5
137.4
137.4
2387
6820
9207
475
158.0
C150
136.8
157.4
157.4
2728
8525
11253
580
210.0
C200
181.9
209.1
209.1
3069
10571
13640
703
n The above information is provided for reference only. For all ratings the user must verify that the selected enclosure will dissipate the total BTUs
generated within the enclosure without allowing the internal ambient to rise above 50
°
C. Enclosure mounting and location must allow for the heatsink
to extend outside the enclosure.
•
When locating the drive allow a minimum clearance from other components of 4.0 inches (101.6 mm) on the top and bottom, 2.0 inches (50.8 mm) on
either side.
•
When mounting the drive, ensure that the heatsink fins are vertical.
With the heatsink exposed to the ambient, the drive will dissipate heat as listed in the Output Current Table above.