SNMP Trap Number

HTTP

1609 UPS Management Software supports WEB Server for remote manager to
obtain the UPS information. Users can use IE or Communicator to connect with
1609 UPS Management Service. Even your computer doesn't have 1609 UPS
Management Software installed you can monitor and control your UPS via
network.

Enable HTTP: Enable or disable the feature of Web service.

HTTP Root: The HTTP root path. All the html and gif files will be
located here.

Port Number: The default port number is 80 but if there is already one
WEB server running you can change 1609 UPS Management Service
HTTP port number to a different number. At the Internet Browser you
can input http://172.16.176.141:2000 in the URL where 2000 is the
assigned port number.

Variable

Trap No. Description

dupsCommunicationLost

1

SEVER: Communication with the UPS failed

dupsCommunicationEstablished

2

INFORMATION: Communication with the UPS reestablished

dupsPowerFail

3

WARNING: Power failed! The UPS is operating on battery power

dupsPowerRestored

4

INFORMATION: Power restored! The utility power restored

dupsLowBattery

5

SEVER: The UPS batteries are low and will soon be exhausted

dupsReturnFromLowBattery

6

INFORMATION: The UPS has returned from a low battery condition

dupsLoadWarning

7

INFORMATION: Loading percent of the UPS over the Load Warning value

dupsNoLongerLoadWarning

8

INFORMATION: Returnd from Load Warning condition

dupsLoadSeverity

9

Warning: Loading percent of the UPS over the Load Severity value

dupsNoLongerLoadSeverity

10

INFORMATION: Returned from Load Severity condition

dupsUPSFault

13

SEVER: A general fault caused in the UPS

dupsBatteryGroundFault

14

SEVER: The UPS battery ground faul

dupsNoLongerBatteryFault

15

INFORMATION: The UPS recovered from battery ground fault

dupsTestInProgress

16

INFORMATION: The UPS test in progress

dupsBatteryTestFail

17

SEVER: The UPS test in progress

dupsFuseFailure

18

SEVER: The UPS fuse failed

dupsFuseRecovered

19

INFORMATION: The UPS fuse recovere

dupsOutputOverload

20

SEVER: The UPS overload

dupsNoLongerOverload

21

INFORMATION: Recovered from UPS overload

dupsOutputOverCurrent

22

SEVER: The UPS output overcurrent

dupsNoLongerOutputOverCurrent

23

INFORMATION: Recovered from UPS overcurrent

dupsInverterAbnormal

24

SEVER: The UPS inverter abnorma

dupsInverterRecovered

25

SEVER: Recovered from UPS inverter abnorma

dupsRectifierAbnormal

26

SEVER: The UPS rectifier abnormal

dupsRectifierRecovered

27

INFORMATION: The UPS recovered from rectifier abnormal

dupsReserveAbnormal

28

SEVER: The UPS rectifier abnorma

dupsReserveRecovered

29

INFORMATION: The UPS rectifier abnormal

dupsLoadOnReserve

30

INFORMATION: The UPS load on reserve

dupsNoLongerLoadOnReserve

31

INFORMATION: The UPS no longer load on reserve

dupsEnvOverTemperature

32

WARNING: The environment overtemperature

DupsNoLongerEnvOverTemperature

33

INFORMATION: The environment recovered from overtemperatur

DupsEnvOverHumidity

34

WARNING: The environment overhumidit

DupsNoLongerEnvOverHumidity

35

INFORMATION: The environment recovered from overhumidity