8ć13 – Rockwell Automation 1395 Discrete Adapter, Rev 3.XX-8.XX User Manual
Page 48

Chapter 8
Parameter Table
8-13
Parameter 558 - [A> Digital Out 1]
508 - [B> Digital Out 1]
Use: Maps Digital Output 1
Program Terminal Units: None
Maximum Value: 15
Minimum Value: 0
Default Value: 10
Description: This parameter has a range of 0 to 15. It establishes which bit
of Discrete Output parameter 450/350 controls the Output 1 relay. When
the bit is set the relay contact closes. The default value for this parameter is
10 which is the bit corresponding to “At Zero Speed” when parameter
450/350 is linked to Logic Status.
Parameter 559 - [A> Digital Out 2]
509 - [B> Digital Out 2]
Use: Maps Digital Output 2
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 15
Default Value: 5
Description: This parameter has a range of 0 to 15. It establishes which bit
of Discrete Output parameter 450/350 controls the Output 2 relay. When
the bit is set the relay contact closes. The default value for this parameter is
5 which is the bit corresponding to “Drive Running” when parameter
450/350 is linked to Logic Status.
Parameter 575 - [A> DAC Scale 1]
525 - [B> DAC Scale 1]
Use: Scale Factor for Analog Output 1
Program Terminal Units: None
Minimum Value: –1
Maximum Value: +1
Default Value: +1
Description: This parameter determines the scale factor or Gain for
Analog Output 1. A
±
32767 digital value from the Drive is converted to a
±
10V DC signal. Before the digital value is converted the Scale Factor is
applied, thus allowing an effective digital range of
±
2048 (32767/16 =
2048 = 10V DC ). This is achieved by programming the Scale Factor to
.0625 or 1/16.