All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

6

Rockwell Automation Publication 1606-RM013A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

7. Output in Buffer Mode

If the input voltage falls below a certain value (transfer threshold level), the DC-UPS starts buffering without any
interruption or voltage dips. Buffering is possible even if battery not fully charged.

Output voltage in buffer mode

nom.

DC 24V

Output voltage is stabilized and independent from
battery voltage

22.45V

±1%, at no load,

22.25V

±1%, at 10A output current

Transfer threshold for buffering

typ.

80mV higher than the output voltage in buffer mode

Ripple and noise voltage

max.

20mVpp

20Hz to 20MHz, 50Ohm

Output current

nom. 10A

Continuously

allowed

15A

< 5s with full output voltage *)

Short-circuit current

min. 17.9A

Load

impedance

100mOhm

**)

max. 21A

Load

impedance

100mOhm

**)

*)

If the output current is in the range between 10A and 15A for longer than 5s, a hardware controlled reduction of the

maximal output current to 10A occurs. If the 10A are not sufficient to maintain the 24V, buffering stops after another 5s.
Buffering will again be possible as soon as the input voltage recovers.

**)

If the nominal output voltage cannot be maintained in buffer mode, the DC-UPS switches off after 5s to save battery

capacity.

Fig. 7-1 Buffering transition, definitions

Buffer mode

Output

voltage

24V

28V

Input

voltage

t

t

Transfer

threshold

500ms/DIV

0V

Output
Voltage

Input Voltage

24V

22.25V at 10A

24V

Fig. 7-3 Available output current in
buffer mode

Fig. 7-4 Output voltage vs. output current
in buffer mode, typ.

Output Current

0

0

5 Sec.

15A

10A

Time

5A

BonusPower

Output Voltage

A

B
C

Continuously available

Available for 5s then auto switching to curve

Buffering will stop after 5s

D

0

0

5

10

15

20

5

10

15

25V

20

25A

Output

Current

A

B

C

D

D

Buffering will stop after 5s

Fig. 7-2 Transfert behavior, typ.