Relay contacts and inhibit input – Rockwell Automation 1606-XL240-UPSE Power Supply Reference Manual User Manual
Page 11
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
11
Bulletin 1606 Switched Mode Power Supplies
14. Relay Contacts and Inhibit Input
The DC-UPS is equipped with relay contacts and signal inputs for remote monitoring and controlling of the unit.
Relay contacts:
Ready:
Contact is closed when battery is charged more than 85%, no wiring failure is recognized, input
voltage is sufficient and inhibit signal is not active.
Buffering:
Contact is closed when unit is buffering.
Replace Battery:
Contact is closed when the unit is powered from the input and the battery quality test (SOH test)
reports a negative result.
Relay contact ratings
max
60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A resistive load
min
1mA at 5Vdc min.
Isolation voltage
max
500Vac, signal port to power port
Signal input:
Inhibit:
The inhibit input disables buffering. In normal mode, a static signal is
required. In buffer mode, a pulse with a minimum length of 250ms is
required to stop buffering. The inhibit is stored and can be reset by
cycling the input voltage. See also section 27.3 for application hints.
7
+
5.1V
3mA
Inhibit
8
-
Signal voltage
max.
35Vdc
Signal current
max.
6mA, current limited
Inhibit threshold
min.
6Vdc, buffering is disabled above this threshold level
max.
10Vdc
Isolation
nom.
500Vac, signal port to power port