All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

Rockwell Automation Publication 1606-RM013A-EN-P — March 2014

13

Bulletin 1606 Switched Mode Power Supplies

16. Terminals and Wiring


Power terminals

Signal terminals

Type

Bi-stable, quick-connect spring-
clamp terminals. IP20 Finger-
touch-proof. Suitable for field-
and factory installation. Shipped
in open position.

Plug connector with screw terminal. Finger-touch-proof
construction with captive screws for 3.5mm slotted
screwdriver. Suitable for field and factory installation.
Shipped in open position. To meet GL requirements,
unused terminal compartments should be closed.

Solid wire

0.5-6mm

2

0.2-1.5mm

2

Stranded wire

0.5-4mm

2

0.2-1.5mm

2

AWG 20-10AWG

22-14AWG

Ferrules

Allowed, but not required

Allowed, but not required

Pull-out force

10AWG:80N, 12AWG:60N,
14AWG:50N, 16AWG:40N
according to UL486E

Not applicable

Tightening torque

Not applicable

0.4Nm, 3.5lb.in

Wire stripping length

10mm / 0.4inch

6mm / 0.24inch

Fig. 16-1 Spring-clamp terminals, connecting a wire

Insert wire

Close the lever

To disconnect wire, reverse the procedure.

Instructions:

a)

Use appropriate copper cables that are designed
for an operating temperature of 60°C.

b)

Follow national installation codes and regulations!

c)

Ensure that all strands of a stranded wire are properly inserted in
the terminal connection!

d)

Up to two stranded wires with the same cross-section are
permitted in one connection point.

17. Reliability


Lifetime expectancy

min.

137 400h

At 10A output current, 40°C

min.

> 15 years

At 5A output current, 40°C

min.

> 15 years

At 10A output current, 25°C

MTBF SN 29500, IEC 61709

886 000h

At 10A output current, 40°C

1 482 000h

At 10A output current, 25°C

MTBF MIL HDBK 217F

397 900

At 10A output current , 40°C, ground benign GB40

545 000

At 10A output current , 25°C, ground benign GB25

The Lifetime expectancy shown in the table indicates the operating hours (service life), and is determined by the
lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours.
Lifetime expectancy is calculated according to the capacitor’s manufacturing specififications. The prediction model
allows a calculation of up to 15 years from date of shipment.

MTBF

stands for Mean Time Between Failures, which is calculated according to statistical device failures and indicates

reliability of a device. It is the statistical representation of the likelihood of failure of a specific unit and does not
necessarily represent the life of a product.