Original instructions, Step 4, Step 5 – Rockwell Automation 445L Installation and Operating Instructions User Manual
Page 21
Muting Controller Box Installation and Operating Instructions
21
R
Original instructions
GuardShield Type 2/Type 4 (440L)
Step 4
Mounting of the Muting Sensors
Step 5
Mounting of the Retroreflectors
Muting with GuardShield Micro 400
For muting a GuardShield Micro 400 safety light curtain use the safety software to create a configuration and download it to the MSR42
controller.
Two-Beam or Four-Beam Muting
The MSR42 offers two beam and four beam muting according to the Muting Types section (page 12). The controller box is delivered by
default with the two-beam T-type muting. Other muting configurations can be selected with the safety software and downloaded with
the optical interface.
Note: Four beam muting is only possible if the Micro 400 safety light curtain is used.
The mounting brackets for the GuardShield 440L are supplied with
the light curtain.
T-slot nut and screws are included with the floor mounting column.
Before mounting, check for height and cable exit position (bottom
or top).
Premount the bracket
Premount the light curtain with the supported screws.
Tighten the screws after aligning.
Note: Only one slot of the GuardShield bracket will fit into
the mounting stand channel.
Before starting to mount the muting sensors, check the section for
the mounting position with respect to the muting type. Mount the
muting sensor according its instruction.
T-slot nut and screws for the RightSight bracket 60-2649 are
supported with the cantilever.
Check for good visibility of the sensor indicator LEDs.
Check the Muting Types section on page 12 for the mounting
position for the chosen muting type.
T-slot nut and screws are provided with the cantilever.