Product technical specifications – TCI HG7 User Manual
Page 52

C O M P O N E N T P A C K A G E O P T I O N ( C P )
COMPONENT PACKAGE OPTION
HG7 I, O, & M Manual
50
Product Technical Specifications
Table 11 lists the major technical specifications and intended environments for the HG7 Harmonic
Filter components.
Table 11 – HG7 “CP” Option Harmonic Filter Components Technical Specifications
Voltage ratings
240, 480 and 600 V, 3 ph, 60 Hz
380 – 415 V, 3 ph, 50 Hz
kVar ratings
3 to 270 kVar depending on voltage.
Load types
3-phase diode bridge rectifier loads such as PWM AC drives
Load power range
7.5 -900 Hp depending on voltage, 4–710kW
Series Reactor Current
ratings
The included series reactors can tolerate 200% of rated current for at
least 3 minutes.
Maximum elevation for all
components
3,000 feet (1,000 meters) as standard. Product must be equipped with
special cooling provisions for operation above this altitude.
Maximum ambient operating
temperature
50°C (122°F) – Open Panel; 40°C (104°F) – Enclosed Panel.
Product must be equipped with special cooling provisions for
operation above this temperature.
Maximum ambient storage
temperature
60°C (140°F)
Maximum humidity,
operating or storage
95%, non-condensing.
Agency approvals or
certifications on components
All components are UL component recognized and can be used to
develop a cUL Listed to UL508A system when designed and built by
a qualified UL certified facility. Components can also be developed
for CSA-C2.2 No. 14 when authorized by CSA.
Insertion Impedance of the
series line reactor
+/- 10% at full load current
Capacitors
Oil filled high endurance design (no PCBs)