Display and keypad – TCI HG7 User Manual
Page 31

P O W E R M O N I T O R P A C K A G E O N L Y
POWER MONITOR OPTION
HG7 I, O, & M Manual
29
Figure 4 – HG2 Protection Monitor Display and Keypad
Display and Keypad
Figure 4 shows the HG2 Protection Monitor display and keypad. Table 4 lists the various component
items and describes their functions.
Table 4 – HG2 Protection Monitor Display and Keypad Features
Item
No.
Name
Description
Function
1
Display
LCD
Displays “OFF” when filter is off.
Displays the value of the selected Operating Parameter.
Displays Fault Code (Fnn) when a fault condition exists.
2
Filter Disabled
Red LED
Illuminated when filter is disabled by fault trip.
3
Filter Enabled
Green LED
Illuminated when filter is operating.
4
UP
(Scroll)
Key
Press and release quickly to display the name of the
selected parameter. Display automatically reverts to
parameter value display after 1 second. Press and hold to
scroll to desired parameter selection.
5
DOWN
(Scroll)
Key
6
SELECT
Key
Press and release quickly to display L #, L A, or L r, phase,
average, or total value selection. Press and hold to scroll to
desired selection.