En50160 statistics log files, Appendix d, In appendix – SATEC EM720 Operation Manual User Manual
Page 199
![background image](/manuals/572127/199/background.png)
Appendix D EN50160 Statistics Log Files
EM720 Power Quality and Revenue Meter
199
Appendix D EN50160 Statistics Log Files
The following tables list the EN50160 evaluation parameters
recorded by the device to the EN50160 statistics data log
files. The second column shows data abbreviations used in
the PAS data log reports. Data log file sections are
highlighted in bold.
EN50160 Compliance Statistics Log (Data Log #9)
Field No.
Designation Description
Power
Frequency
1
Nnv
Number of non-valid 10-sec intervals
2
N
Number of valid 10-sec intervals
3
N1
Number of incidents ±1%, N1
4
N2
Number of incidents +4%/-6%, N2
5
N1/N, %
EN50160 compliance ratio, N1/N
6
N2/N, %
EN50160 compliance ratio, N2/N
7
Freq Min
Minimum frequency
8
Freq Max
Maximum frequency
Supply
Voltage
Variations
1
Nnv
Number of non-valid 10-min intervals
2
N
Number of valid 10-min intervals
3
N1
Number of polyphase incidents ±10%, N1
4
N2
Number of polyphase incidents +10/-15%, N2
5
N1/N, %
EN50160 compliance ratio, N1/N
6
N2/N, %
EN50160 compliance ratio, N2/N
7
V1 N1
Number of incidents ±10% on phase V1
8
V1 Min
Minimum voltage on phase V1
9
V1 Max
Maximum voltage on phase V1
10
V2 N1
Number of incidents ±10% on phase V2
11
V2 Min
Minimum voltage on phase V2
12
V2 Max
Maximum voltage on phase V2
13
V3 N1
Number of incidents ±10% on phase V3
14
V3 Min
Minimum voltage on phase V3
15
V3 Max
Maximum voltage on phase V3
Rapid
Voltage
Changes
1
N1
Number of polyphase incidents
2
V1 N1
Number of incidents on phase V1
3
V1 dV%
Maximum voltage variation on phase V1, dV/Un%
4
V2 N1
Number of incidents on phase V2
5
V2 dV%
Maximum voltage variation on phase V2, dV/Un%
6
V3 N1
Number of incidents on phase V3
7
V3 dV%
Maximum voltage variation on phase V3, dV/Un%
Flicker
1
Nnv
Number of non-valid 2-hour intervals
2
N
Number of valid 2-hour intervals
3
N1
Number of polyphase incidents Plt >1%, N1
4
N1/N, %
EN50160 compliance ratio, N1/N
5
V1 N1
Number of incidents Plt > 1% on phase V1
6
V1 Plt Max
Maximum Plt on phase V2
7
V2 N1
Number of incidents Plt > 1% on phase V2