page 46 — dca70SSJU4i 60 hz generator • operation and parts manual — rev. #2 (04/09/14)

MaiNteNaNCe

auto regeneration procedure

Auto regeneration process will automatically occur. No

operator action is required for this process. Allow the engine

to run for at least 30 minutes to complete the automatic

regeneration process.
Reference Table 17 for the various soot level stages for

the DPF system.

table 17. automatic dpF System

Soot Level 0 Soot Level 1 & 2

Soot Level 3

Soot Level 4

Soot Level 5

Controller Message

N/A

N/A

FILTER CLEAN

REQUESTED

SOOT LEVEL

HIGH!

SOOT LEVEL

VERY HIGH!

DPF Condition

Regen Not

Required

Moderate Soot

Level

High Soot Level

Very High Soot

Level

Service DPF

(Soot Only)

Pre-Alarm Lamp

N/A

N/A

Blinking

ON

ON

Shutdown Lamp

N/A

N/A

N/A

N/A

ON

Engine

Shutdown

NOTICE

Generator derating occurs during soot levels 4 and 5.

Soot level 5 will cause the generator to shutdown If

this condition occurs contact your nearest authorized

service center.

NOTICE

dO NOT perform regeneration in conditions where it

may be unsafe due to high exhasust temperatures.

NOTICE

The area above and around the generator during

the regeneration process should be free of any type

of debris, flammable or conbustible materials, as

temperatures during the regeneration process can

reach as high 1,022 °F (550 °C).