dca70SSJU4i 60 hz generator• operation manual — rev. #2 (04/09/14) — page 31

3Ø-600v auto-transformer

3Ø, 600 VAC can be achieved via the auto-transformer

module. This module provides the necessary electronics

to convert the 3Ø, 480 VAC inut voltage to a 3Ø, 600 VAC

output voltage.
The 3Ø, 600 VAC ouput voltage cannot be achieved unless

the voltage selector switch (Figure 29) is placed in the 3Ø,

480/277 position.

Figure 29. Voltage Selector Switch

3Ø-240/139V Position (600 VAC Auto-Transformer)

3Ø-600vac load connections

1. Loosen the latches on the control box enclosure and

open the door.

2. Drill a 1-1/2 inch hole at the bootom control box

enclosure as shown in Figure 30.

Figure 30. Control Box Enclosure (Drilling)

daNgeR

When connecting the load wires make sure the

generator is

oFF. The possibility of electrocution exists

causing severe bodily harm even death!

CIRCUIT BREAKER

ENCLOSURE

DRILL

NEW HOLE

(1-1/2” DIA.)

STRAIGHT

FITTING

LOCK

RING

BUSHING

3. After drilling, make sure all shavings and debris have

been removed from the enclosure.

4. Install customer supplied conduit, fittings and bushing

through enclosure hole opening.

5. Next, route the customer supplied 5 wires through the

straight conduit fitting.

6. Connect the 3 load wires (

Red, BlacK and Blue)

to the load side (bottom) of the circuit breaker,

t1, T2

and

t3 respectively. Reference Figure 31

Figure 31. Control Box Enclosure

Load Connections

7. Connect the neutral wire (

White) to the neutral bus

bar.

8. Connect the ground wire (

gReeN) to the ground

terminal.

9. Torque all wires to 45 lbf-in (5 N.m).
10. Once all wires have been securely tighten, close

control box enclosure door and securely tighten the

control box door latches.

L1

T1 T2 T3

L2 L3

70 AMP

CIRCUIT BREAKER

LOAD

WIRES

FROM

600 VAC

AUTO

TRANSFORMER

NEUTRAL BUS BAR

GROUND

TERMINAL

600 VaC CONNeCtiONs