beautypg.com

Output terminal panel familiarization – Multiquip DCA70SSJU4i User Manual

Page 24

background image

page 24 — dca70SSJU4i 60 hz generator • operation and parts manual — rev. #2 (04/09/14)

OUtpUt terMiNaL paNeL FaMiLiariZatiON

120 vac gFci receptacles

There are two 120 VAC, 20 amp GFCI (Duplex Nema 5-20R)

receptacles provided on the output terminal panel. These

receptacles can be accessed in any

voltage change-over

board configuration. Each receptacle is protected by a 20

amp circuit breaker. These breakers are located directly

above the GFCI receptacles. Remember the load output

(current) of both GFCI receptacles is dependent on the

load requirements of the U, V, and W output terminal lugs.
Pressing the

reset button resets the GFCI receptacle after

being tripped. Pressing the

test button (See Figure 9) in

the center of the receptacle will check the GFCI function.

Both receptacles should be tested at least once a month.

Figure 9. G.F.C.I. Receptacle

twist lock dual voltage 120/240 vac receptacles

There are three 240/139V, 50 amp auxiliary twist-lock (CS-

6369) receptacles (Figure 10) provided on the output

terminal panel. These receptacles can

only be accessed

when the voltage change-over board is configured for

single-phase 240/120 application

Figure 10. 240/139V Twist-Lock Auxiliary

Receptacles

Each auxiliary receptacle is protected by a 50 amp circuit

breaker. These breakers are located directly above the

GFCI receptacles. Remember the load output (current) on

all three receptacles is dependent on the load requirements

of the

output terminal lugs.

Turn the

voltage regulator control knob (Figure 11) on

the control panel to obtain the desired voltage. Turning the

knob clockwise will

increase the voltage, turning the knob

counter-clockwise will

decrease the voltage.

Figure 11. Voltage Regulator Control Knob

removing the plastic Face plate (hard Wire

hookup panel)

The

Output Terminal Lugs are protected by a plastic

face plate cover (Figure 12). Un-screw the securing bolts

and lift the plastic terminal cover to gain access to the

terminal enclosure.
After the load wires have been securely attached to the

terminal lugs, reinstall the plastic face plate.

Figure 12. Plastic Face Plate

(Output Terminal Lugs)