3 fault indications, Fault indications, Troubleshooting and fault elimination – Lenze 8240 frequency inverters User Manual
Page 53
Troubleshooting and fault elimination
UOOu_^MTMO
8-3
L
8.3
Fault indications
Display
Fault
Cause
Remedy
---
No fault
-
-
EEr
External fault (TRIP-Set)
A digital input assigned to the TRIP-Set
function has been activated
Check external encoder
H05
Internal fault
Contact Lenze
LU
Undervoltage
DC-bus voltage too low
D
Check mains voltage
D
Check supply module
OC1
Short circuit
Short circuit
Find out cause of short circuit; check cable
Excessive capacitive charging current
of the motor cable
Use motor cable which is shorter or of lower
capacitance
OC2
Earth fault
Grounded motor phase
Check motor; check cable
Excessive capacitive charging current
of the motor cable
Use motor cable which is shorter or of lower
capacitance
OC3
Overload inverter during
acceleration or short circuit
Acceleration time too short (C012)
D
Increase acceleration time
D
Check drive selection
Defective motor cable
Check wiring
Interturn fault in the motor
Check motor
OC4
Overload controller during
deceleration
Deceleration time too short (C013)
D
Increase deceleration time
D
Check the selection of the brake resistor or
connect the brake chopper
OC5
I x t overload
Frequent and too long acceleration
processes with overcurrent
Check drive dimensioning
Permanent overload with
I
motor
> 1.05 x I
Nx
OC6
Overload motor
Motor is thermally overloaded, for
instance, because of
D
impermissible continuous current
D
Check drive selection
D
frequent or too long acceleration
processes
D
Check the setting under C120
OH
Heat sink temperature is higher
than the value set in the
controller
Ambient temperature
T
amb
> +40
°C or +50 °C
D
Allow controller to cool and ensure
ventilation
D
Check the ambient temperature in the
control cabinet
Heat sink very dirty
Clean heat sink
Incorrect mounting position
Change mounting position
OH3
PTC monitoring (TRIP)
Motor too hot because of excessive
current or frequent and too long
acceleration
Check drive dimensioning
PTC not connected
Connect PTC or switch off monitoring
(C0585=3)
OH4
Overtemperature unit
Inside unit too hot
D
Reduce controller load
D
Improve cooling
D
Check fan in the controller
OH51
PTC monitoring (Warning)
Motor too hot because of excessive
current or frequent and too long
acceleration
Check drive selection
PTC not connected
Connect PTC or switch off monitoring