2 power connections, 1 mains connection, Power connections – Lenze 8240 frequency inverters User Manual
Page 22: Mains connection, Installation
Installation
4-6
UOOu_^MTMO
L
4.2.2
Power connections
4.2.2.1
Mains connection
Types 8221 to 8227
Types 8241 to 8246
PE
+UG
-UG
L1
L2
L3
mb
iN
iO
iP
Jrd
Hrd
➀
➁
Correct screen connection with screened cables:
D
Connect the screen with the conductive mounting plate
using a suitable clamp.
D
To improve the screen connection: Connect screen
additionally at the stud PE next to the power
connections.
Connect screen correctly
(required parts in the accessory kit):
D
Screw screen sheet
➀
on the fixing bracket
➁
.
D
Fix screen using cable lugs. Do not use the screen for
strain relief!
D
To improve the screen connection: Connect screen
additionally at the stud PE next to the power
connections.
cfd QJQ
mêçéçë~д Сзк г~бел ЕзееЙЕнбзе UOOuLUOQu
D
`зееЙЕн нЬЙ г~бел Е~ДдЙл пбнЬ нЬЙ лЕкЙп нЙкгбе~дл iNI iOI iPK
J qáÖÜíÉåáåÖ нзкимЙл
Terminals
Type
L1, L2, L3, +UG, -UG
PE connection
8221 - 8223
4 Nm (35 lbin)
8224 - 8225
7 Nm (62 lbin)
8226 - 8227
12 Nm (106.2 lbin)
8241 - 8246
0.5 ... 0.6 Nm (4.4 ... 5.3 lbin)
3.4 Nm (30 lbin)