Configuration
7-2
UOOu_^MTMO
L
7.2
Code table
How to read the code table:
Column
Abbreviation
Meaning
Code
C013
Code C013
D
The parameter of the code can be different in PAR1 and PAR2.
D
The parameter value is accepted immediately (ONLINE).
C009*
D
The parameter value of the code is always the same in PAR1 and PAR2, but is
always displayed in PAR1.
C001
¿
D
The parameter value of the code will be accepted after pressing SH+PRG.
[C002]
D
The parameter value of the code will be accepted after pressing SH+PRG but
only if the controller is inhibited.
Name
820X
Name of the code.
Unit-specific setting possibilites (here for 820X).
Without unit designation the code is valid for all unit types.
Lenze
Factory setting of the code
*
The column ”Important” contains further information
Selection
1
{1 %}
99 Minimum value
{smallest step/unit}
maximum value
Info
-
Meaning of the code
IMPORTANT
-
Additional, important explanations of the code
Code
Name
Possible settings
IMPORTANT
Lenze
Selection
Info
C001
¿ Operating mode
-0-
-0-
Setpoint selection via term. 8
Control via terminals
Parameter setting via 8201BB
-1-
Setpoint selection via 8201BB or via
LECOM
Control via terminals
Parameter setting via 8201BB
-2-
Setpoint selection via term. 8
Control via terminals
Parameter setting via LECOM
-3-
Setpoint selection via LECOM
Control via LECOM
Parameter setting via LECOM
[C002]* Parameter set
-0-
Function executed
-1-
Overwrite PAR1 with factory setting
-2-
Overwrite PAR2 with factory setting
-3-
Overwrite PAR1 and PAR2 with the
data of the operating module
-4-
Overwrite PAR1 with the data of the
operating module
-5-
Overwrite PAR2 with the data of the
operating module
-6-
Transmit PAR1 and PAR2 to the
operating module
C004
¿ Switch-on display
-0-
-0-
Field frequency f
d
-1-
Controller load
-2-
Motor current