Configuration – Lenze 8240 frequency inverters User Manual
Page 48
![background image](/manuals/566200/48/background.png)
Configuration
7-4
UOOu_^MTMO
L
Code
IMPORTANT
Possible settings
Name
Code
IMPORTANT
Info
Selection
Lenze
Name
C014
¿ Operating mode
820X
-0-
-0-
Linear characteristic V~f
d
with auto
boost
-1-
Square characteristic V~f
d
2
with
auto boost
-2-
Linear characteristic V~f
d
with
constant V
min
boost
-3-
Square characteristic V~f
d
2
with
constant V
min
boost
821X/822X/
824X
-4-
-4-
Motor-current control
C015 V/f-rated frequency
820X
50.0
30.0
{0.1Hz}
960.0
821X
50.0
7.5
{0.1Hz}
960.0
30.0
{0.1Hz}
960.0
(Software 2x)
(Software 1x)
822X/824X
50.0
7.5
{0.1Hz}
960.0
C016 V
min
setting
820X
*
0
{1 %}
40
* depends on the unit
821X/822X/
824X
0
0
{1 %}
40
C017 Threshold Q
min
0.0
0.0
{0.1Hz}
480.0
C018
¿ Chopper frequency
¿
821X/822X/824X
-1-
-0-
4 kHz
-1-
8 kHz
-2-
12 kHz
-3-
16 kHz
-4-
12 kHz noise optimized
-5-
16 kHz noise optimized
C019 Threshold auto DC
brake
821X/822X/824X
0.1
0.1
{0.1Hz}
5.0
C021 Slip
compensation
820X
0
0
{1 %}
12
821X
0
0
{1 %}
20
0
{1 %}
12
(Software 2x)
(Software 1x)
822X/824X
0
0
{1 %}
20
C022 I
max
limit
motor mode
150
30
{1 %}
150
C023 I
max
limit
generator mode
80
30
{1 %}
110
C034
¿ Master current
-0-
-0-
0 to 20mA /
0 to 5V / 0 to 10V
-1-
4 to 20mA
C036 Voltage for DC brake
*
0
{1 %}
40
* depends on the unit
C037 JOG value 1
20
0
{1Hz}
480
C038 JOG value 2
30
0
{1Hz}
480
C039 JOG value 3
40
0
{1Hz}
480
C050* Output frequency
Only display
C052* Motor voltage
Only display
C054* Motor current
Only display
Show/Hide Bookmarks