Type
Mains input L1, L2, L3, PE/motor connection U, V, W, PE
yp
Operation with mains filter/choke only
Fuse F1, F2, F3
E.l.c.b.
Cable cross-section
1)
VDE
UL
VDE
mm
2
AWG
8221
M 50A
50A
--
16
5
8222
M 63A
63A
--
25
3
8223
M 80A
80A
--
25
3
8224
M 125A
125A
--
70
2 / 0
8225
M 160A
175A
--
95
3 / 0
8226
M 160A
175A
--
95
3 / 0
8227
M 200A
200A
--
120
4 / 0
8241
M 6A
5A
B 6A
1
17
8242
M 6A
5A
B 6A
1
17
8243
M 10A
10A
B 10A
1.5
15
8244
M 10A
10A
B 10A
1.5
15
8245
M 20A
20A
B 20A
4
11
8246
M 32A
25A
B 32A
6
10
1)