Commissioning
5-2
UOOu_^MTMO
L
5.2
Short set-up with factory setting
5.2.1
Switch-on sequence
Step
1.Switch on mains voltage
2.Select the direction of rotation.
D
CW rotation:
- Apply a LOW signal to terminal E4 (0...+3V).
D
CCW rotation:
- Apply a HIGH signal to terminal E4 (+12...+30V).
3.Select the setpoint.
Apply a voltage 0...+10 V to terminal 8.
4.Enable the controller.
Apply a HIGH signal (+12...+30V) to terminal 28.
5.The drive is now operating according to factory setting.
5.2.2
Factory setting of the most important drive parameters
Setting
Code
Factory setting
Adaption to
the application
Operating mode
C001
-0-
Setpoint selection via terminal 8
Control via terminals
Parameter setting via 8201BB
See the Code
Table
chapter 7.2
Terminal configuration
C007
-0-
E4
E3
E2
E1
CW/CCW DC brake
JOG1/2/3
See the Code
Table
chapter 7.2
Machine data
Chapter 5.3 ff.
Speed range
Min. field frequency
C010
0.0 Hz
See chapter
p
g
Max. field frequency
C011 50.0 Hz
p
5.3.1
Acceleration and
deceleration
Acceleration time
C012
5.0 s
See chapter
5 3 2
deceleration
times
Deceleration time
C013
5.0 s
5.3.2
Current limit
Motor mode
C022
150 %
See chapter
values
Generator mode
C023
80 %
p
5.3.3
Drive performance
Chapter 5.4 ff.
Current,
torque
Operating mode
C014
-4-
Motor-current control
Motor-current
control see
torque,
power
V/f rated frequency
C015 50.0 Hz
control, see
chapter 5.4.2.1
power
characteristic
V
min
setting
C016
0 %
c apte 5
V/f characteristic
control see
Slip compensation
C021
0 %
control, see
chapter 5.4.2.2