3 maloperation of the drive, 2 fault analysis using the history buffer, Maloperation of the drive – Lenze 8240 frequency inverters User Manual
Page 52: Fault analysis using the history buffer, Troubleshooting and fault elimination
![background image](/manuals/566200/52/background.png)
Troubleshooting and fault elimination
8-2
UOOu_^MTMO
L
8.1.3
Maloperation of the drive
Maloperation
Possible causes
Motor does not rotate
D
DC-bus voltage too low
(red LED is blinking every 0.4 s; message LU is displayed)
D
Controller inhibited
(green LED is blinking, display of the operating module: OFF, STOP or
AS_LC)
D
Setpoint = 0
D
DC braking active
D
Quick-stop function active
D
JOG setpoint activated and JOG frequency = 0
D
Fault is indicated (see chapter 8.3 )
D
Mechanical motor brake is not released
Motor does not rotate smoothly
D
Defective motor cable
D
Maximum current C022 and C023 too low
D
Motor underexcited or overexcited (check parameter setting)
Current consumption of motor too
high
D
Setting of C016 too high
D
Setting of C015 too low
D
C088 and C091 are not adapted to the motor data.
8.2
Fault analysis using the history buffer
D
qЬЙ Ьблнзку ДмССЙк бл млЙЗ нз нк~ЕЙ С~ìäíëK qЬЙ С~мдн гЙлл~ЦЙл ~кЙ лнзкЙЗ бе нЬЙ
Ьблнзку ДмССЙк бе нЬЙ зкЗЙк зС нЬЙбк çÅÅìêêÉåÅÉK
D
qЬЙ Ьблнзку ДмССЙк Ь~л Q гЙгзку дзЕ~нбзел пЬбЕЬ Е~е ДЙ ~ЗЗкЙллЙЗ об~
ÅçÇÉëK
Structure of the history buffer
Code
C0168
Entry
Note
C161
Memory locations 1
Active fault
If the fault is no longer active or has been
acknowledged:
C162
Memory location 2
Last fault
acknowledged:
D
The contents of the memory locations 1-3 will be
saved in a ”higher” location.
C163
Memory location 3
Last but one fault
g
D
The contents of the memory location 4 will be
eliminated from the history buffer and cannot be
C164
Memory location 4
Last but two fault
y
read any longer.
D
Memory location 1 will be deleted
(= no active fault).
Show/Hide Bookmarks