Configuration – Lenze 8240 frequency inverters User Manual
Page 49
Configuration
UOOu_^MTMO
7-5
L
Code
IMPORTANT
Possible settings
Name
Code
IMPORTANT
Info
Selection
Lenze
Name
C056* Controller load
Only display
C061* Heat sink
temperature
Only display
C079 Oscillation damping
Is not transferred when
transferring
822X/824X
5
0
{1}
80
transferring
parameters via the
operating module.
C088 Rated motor current
821X/822X/824X
*
0.0 ... 1.2 ¡ rated output current
* depends on the unit
C091 Motor cos
j
821X/822X/824X
*
0.4
{0.1}
1.0
* depends on the unit
C093* Type
Only display
820X
820X
821X
821X
822X/824X
822X
C099* Software version
Only display
820X
82 1x
(Software 1x)
821X
82 2x
(Software 2x)
82 1x
(Software 1x)
822X/824X
82 1x
(Software 1x)
C105 Deceleration time
quick stop
821X/822X/824X
5.00
0.00
{0.01s}
999.00
C106 Holding time for
autom. DC injection
brake
820X
0.00
0.00
{0.01s}
50.00
821X/822X
824X
0.02
0.00
{0.01s}
999.00
C108* Gain (C111)
820X
220
0
{1}
255
821X
128
0
{1}
255
822X/824X
128
0
{1}
255
C111
¿ Monitor signal
-0-
-0-
Field frequency
-1-
Controller load
-2-
Motor current
-3-
DC-bus voltage
C117
¿ Function relay K2
822X/824X
-0-
-0-
Ready for operation
-1-
TRIP fault message
-2-
Motor is running
-3-
Motor is running / CW rotation
-4-
Motor is running / CCW rotation
-5-
Field frequency f
d
= 0
-6-
f
dSet
reached
-7-
Q
min
reached
-8-
I
max
reached
-9-
Overtemperature (
J
max
-10
°C)
-10-
TRIP or Q
min
or IMP
-11-
PTC warning