6 commissioning, 1 before initial switch-on, Commissioning – Lenze E94AYCEN User Manual
Page 26: Before initial switch-on

E94AYCEN communication manual (Ethernet)
Commissioning
Before initial switch-on
26
L
EDS94AYCEN EN 9.0 - 09/2012
6
Commissioning
During commissioning, system-related data such as motor parameters, operating
parameters, responses, and parameters for fieldbus communication are defined for the
drive. For Lenze devices, this is done via the codes.
The codes of the drive and for communication are saved non-volatilely as a data set in the
memory module.
In addition to codes for the configuration, there are codes for diagnosing and monitoring
the nodes.
6.1
Before initial switch-on
Note!
When parameterising the communication module, please note that the code
number depends on the slot of the Servo Drive 9400 into which the
communication module is plugged.
The first two digits of the code number indicate the slot:
• C13nnn for slot MXI1
Parameters of the communication module for slot MXI1
• C14nnn for slot MXI2
Parameters of the communication module for slot MXI2
Additionally set the
Parameters of the standard device that are relevant to
.
Stop!
Before switching on the Servo Drive 9400 and the communication module for
the first time, check the entire wiring for completeness, short circuit and earth
fault.